Ensure that the total power requirement of the equipment to be protected does not exceed the rated 
output power of the UPS. (output power for your unit is indicated on the rating label on the rear panel). 
 
 
When using the 120V split phase outputs make sure that the load per 120V output does not exceed half 
the rating.  
 
 
The UPS may only be installed by trained personnel. The UPS must be grounded when in use: Connect 
the UPS to a single phase, three wire AC source equipped with an earth connection. 
 
 
Use insulated copper input and output wiring, rated 90°C derated to 40°C, wire size based on the 
ampacities given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993. 
 
 
This wiring shall have the following minimum sizes: 
 
 INPUT 
WIRING: 
 Utility 
voltage 
UPS model 
120V 208V 240V 
LP 5-11U  
6 AWG 
10 AWG 
10 AWG 
LP 6-11U 
4 AWG 
8 AWG 
10 AWG 
LP 8-11U 
N/A 
6 AWG 
8 AWG 
LP 10-11U 
N/A 
4 AWG 
6 AWG 
 
Table 2. Input wiring 
 
 
 OUTPUT 
WIRING: 
 Output 
voltage 
UPS model 
120V 208V 240V 
LP 5-11U  
8 AWG 
10 AWG 
10 AWG 
LP 6-11U 
8 AWG 
10 AWG 
10 AWG 
LP 8-11U 
6 AWG 
8 AWG 
8 AWG 
LP 10-11U 
4 AWG 
8 AWG 
8 AWG 
 
Table 3. Output wiring 
 
 
 
TIGHTENING TORQUE FORCE: 
UPS model 
Tightening torque force 
LP 5/6-11U/120V 
22 Lbs/inch 
All other models 
18-20 Lbs/inch 
 
Table 4. Tightening torque force