LX: OPM_LPU_11U_5K0_10K_1US_V030
 
8
 
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
 
Digital Energy
 LP Series
g
 
3.4 
Automatic Bypass Switch  
 
If the output converter is unable to deliver the demanded output power because of overload or 
overtemperature, the automatic bypass switch will automatically transfer the load to the utility. When the 
situation is corrected the UPS will switch back to normal operation, i.e. the load is tranferred back to the output 
converter. Though the automatic bypass switch is shown as a simple mechanical switch in figures 2-5, the 
transfers are done by means of thyristors, i.e. electronically, without any interruption of the power supplied to 
the load. 
In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to 
protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the 
software in order to protect the UPS and connected equipment.’ 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
If a power failure occurs during bypass operation, load power may be lost. If the UPS functions under overload 
conditions it may not be able to protect the load. 
 
 
3.5 
Manual Bypass Switch (Service switch) 
 
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-
position switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly 
connected to the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is 
possible without interruption of the power supplied to the load.  
 
CAUTION:
  
REFER SERVICE TO QUALIFIED PERSONNEL ONLY
 
THE RFI FILTERS AND OUTPUT TRANSFORMER ARE ALWAYS ACTIVE. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  
Figure 4 . Bypass operation: Automatic bypass
Figure 5 . Bypass operation: Manual bypass
BYPASS 
FILTER 
P.F. = 1 
CONVERTER/ 
RECTIFIER/ 
BATTERY 
CHARGER 
BACKFEED 
PROT. 
OPTIONAL 
BATTERY 
EXTENSION 
BATTERY 
MICROPROCESSOR CONTROL 
SYSTEM
ON/OFF 
OUTPUT 
CONVERTER 
MANUAL BYPASS
SWITCH
UTILITY INPUT 
RFI 
FILTER 
OPTION 
SLOTS FOR:
 
RPA CARD 
 
SNMP CARD
 
RELAY CARD
STANDARD 
INSTALLED: 
 
RS232/ 
CONTACT 
INTERFACE 
FRONT 
PANEL 
TO LOAD 
RFI 
FILTER 
STATIC 
BYPASS 
OUTPUT 
TRANSFORMER 
BYPASS 
FILTER 
P.F. = 1 
CONVERTER/ 
RECTIFIER/ 
BATTERY 
CHARGER 
BACKFEED 
PROT. 
OPTIONAL 
BATTERY 
EXTENSION 
MICROPROCESSOR CONTROL 
SYSTEM
ON/OFF 
OUTPUT 
CONVERTER 
MANUAL BYPASS 
SWITCH
UTILITY INPUT 
RFI 
FILTER 
OPTION 
SLOTS FOR:
 
RPA CARD 
 
SNMP CARD
 
RELAY CARD
STANDARD 
INSTALLED: 
 
RS232/ 
CONTACT 
INTERFACE 
FRONT 
PANEL 
TO LOAD 
RFI 
FILTER 
STATIC 
BYPASS 
OUTPUT 
TRANSFORMER