Configuring the Modbus Models
                                                                      
31007492
 42
3.6 Your Configuration Commands
&! &!%!&"&! ""   $   "" !  # 
#! "  #    %  ! % "   
Command
Action
Range
V
Select a configuration screen or Help screen
1 ... 8
P
Select a port to be configured
1 ... 4
N
Enter a Modbus slave device address
1 ... 247
T
Enter the port type
M = Master
S = Slave
N = Network
X = Silent Master Network
B
Enter the baud rate
50, 300, 1200, 1800, 2000, 2400,
3600, 4800, 7200, 9600, 19200
S
Enter the stop bits
1 or 2 (Note 1)
R
Enter the parity mode
N = None
O = Odd
E = Even
M
Enter the communication mode
A = ASCII
R = RTU
Y
Enter the port priority
1 ... 4
L
Enter the link timeout value
1 ... 3000, in multiples of 100 ms
F
Enter the modem booster selection
Y = Yes
N = No
W
Write the configuration parameters to all four ports
D
Initialize all four ports with default parameters
?
Display Help for the current configuration screen
E
Enter a Modbus address and five–byte routing path into
the Modbus Address Map table on the V2 or V3 screen.
When you use this command, enter the following:
–  the E command
–  the table location (1 ... 64) for your entry
–  the Modbus address (1 ... 255) to be mapped
–  the five bytes of routing (1 ... 255 in each byte).
Entry format:
EYY  MM  XX  XX  XX  XX  XX
where:
E = Modbus Address Map command
YY = location (1 ... 64) in the table
MM = Modbus address (1 ... 255)
XX = each byte (1 ... 255) in the path.
Notes
 !       " $ 
" "! !"" ! ! #" "  " "! %"  " "