Configuring the Modbus Models
31007492
42
3.6 Your Configuration Commands
&! &!%!&"&! "" $ "" ! #
#! " # % ! % "
Command
Action
Range
V
Select a configuration screen or Help screen
1 ... 8
P
Select a port to be configured
1 ... 4
N
Enter a Modbus slave device address
1 ... 247
T
Enter the port type
M = Master
S = Slave
N = Network
X = Silent Master Network
S = Slave
N = Network
X = Silent Master Network
B
Enter the baud rate
50, 300, 1200, 1800, 2000, 2400,
3600, 4800, 7200, 9600, 19200
3600, 4800, 7200, 9600, 19200
S
Enter the stop bits
1 or 2 (Note 1)
R
Enter the parity mode
N = None
O = Odd
E = Even
O = Odd
E = Even
M
Enter the communication mode
A = ASCII
R = RTU
R = RTU
Y
Enter the port priority
1 ... 4
L
Enter the link timeout value
1 ... 3000, in multiples of 100 ms
F
Enter the modem booster selection
Y = Yes
N = No
N = No
W
Write the configuration parameters to all four ports
D
Initialize all four ports with default parameters
?
Display Help for the current configuration screen
E
Enter a Modbus address and five–byte routing path into
the Modbus Address Map table on the V2 or V3 screen.
the Modbus Address Map table on the V2 or V3 screen.
When you use this command, enter the following:
– the E command
– the table location (1 ... 64) for your entry
– the Modbus address (1 ... 255) to be mapped
– the five bytes of routing (1 ... 255 in each byte).
– the table location (1 ... 64) for your entry
– the Modbus address (1 ... 255) to be mapped
– the five bytes of routing (1 ... 255 in each byte).
Entry format:
EYY MM XX XX XX XX XX
EYY MM XX XX XX XX XX
where:
E = Modbus Address Map command
YY = location (1 ... 64) in the table
MM = Modbus address (1 ... 255)
XX = each byte (1 ... 255) in the path.
YY = location (1 ... 64) in the table
MM = Modbus address (1 ... 255)
XX = each byte (1 ... 255) in the path.
Notes
!
" $
" "! !"" ! ! #" " " "! %" " "