Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-28  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Emerson EC20 Series PLC 
A. HMI factory setting 
Baud rate: 19200, 8, Even, 1 (RS-232). 
PLC station number: 0. 
Control area/status area: D0 / D10. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data Length 
Data Word 
Dn 
n: 0-7999 
N/A 
Word 
Special Data Word 
SDn 
n: 0-255 
N/A 
Word 
Data Word 
Zn 
n: 0-15 
N/A 
Word 
Timer Tn 
n: 
0-255 
N/A 
Word 
Counter Cn 
n: 
0-199 
N/A 
Word 
DoubleWord Counter 
CDWn 
n: 200-255 
N/A 
DWord 
DoubleWord Data Word 
DDWn 
n: 0-7998 
N/A 
DWord 
Contacts 
Read/Write Range 
Contact Type 
Format 
Word No. 
Bit No. 
External Output Relay 
Yb 
N/A 
b: 0-377(Octal) 
External Input Relay 
Xb 
N/A 
b: 0-377(Octal) 
Internal Relay 
Mb 
N/A 
b: 0-1999 
Special Internal Relay 
SMb 
N/A 
b: 0-255 
Status Relay 
Sb 
N/A 
b: 0-991 
Timer Tb 
N/A 
b: 
0-255 
Counter Cb 
N/A 
b: 
0-255 
NOTE
  
PLC Communication Settings: 
1)  Emerson EC20 series PLC has two communication ports, COM0 and COM1. They are provided for the 
communication protocol for connecting to PC, Modbus communication protocol and user-defined 
protocol. The default setting is COM0 to be enabled only, so the user needs to set the communication 
mode as Modbus RTU via PC software before using it. 
2)  COM1 supports RS-232 and RS-485.