9.3.8 POPIT 
Labels 
D9412GV3 off-board points are numbered 9 to 127 
and 129 to 247. The D7412GV3 uses Points 9 to 75 
only. The D9412GV3 reserves Points 128 and 248 for 
internal use. POPITs must be connected for Points 
129 to 247 to expansion loops connected to POPEX 
#2.  
Two sheets of peel-off POPIT labels are supplied with 
the D8125 POPEX Module. Use the sheet marked 
“Bank1” for Points 9 to 127. Use the sheet marked 
“Bank2” for Points 129 to 247. 
Each label has two parts. Place the smaller part (with 
only the point number) on the chip. Place the larger 
part with the switch settings on the base of the 
POPIT. Set the switches and cover the POPIT.  
Do not program two POPITs for the same point 
number. After programming all the points, perform a 
Service Walk Test. Refer to Section 4.10 Service 
Walk Test 
on page 44. If a point does not test, check 
the programming for a duplicated address. 
Walk Test and Service Walk Test Do Not Show 
Extra Points:
 If the point assignment switches on a 
POPIT or OctoPOPIT are set incorrectly, missing and 
extra points can occur. If the same point number is 
assigned to two or more POPITs or OctoPOPITs, 
none of the points with that number test correctly. 
Refer to Section 9.1 Point (Zonex) Bus: D9412GV3 
Terminals and D7412GV3 Terminals 
on page 36
 
For UL 864 Commercial Fire applications, 
refer to Installing Combination Fire and 
Intrusion Alarm Systems
 in the 
D9412GV3/D7412GV3 Approved 
Applications Compliance Guide
  
(P/N: F01U143069) for important 
information about combination fire and 
intrusion systems. 
9.4 D8128D 
OctoPOPIT 
Module 
 
Modules D8128, D8128A, or D8128B are 
incompatible with the D9412GV3 or 
D7412GV3. Use only the D8128D 
OctoPOPIT Module. Using Modules 
D8128, D8128A, or D8128B can cause 
intermittent Missing and Restoral Reports. 
9.4.1 Description 
The D8128D OctoPOPIT Module combines the 
functions of the D8125 POPEX Module and the 
D9127 POPIT Modules to provide eight off-board 
points in a single module. You can wire both D8128D 
OctoPOPIT and D8125 POPEX Modules in parallel to 
the Zonex Bus terminals on the same control panel. 
Review Section 6.0 Power Outputs on page 26 to 
ensure that there is enough power for the 
OctoPOPITs and other powered devices that will be 
connected to the system. 
Up to thirty D8128D Modules can be connected to the 
D9412GV3 Control Panel. Up to nine D8128Ds can 
be connected to the D7412GV3 Control Panel (three 
points can be used on the last OctoPOPIT).