Bosch d9412gv3 Manual De Usuario

Descargar
Página de 76
D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0  
Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
44
 
9.4.3 Installation 
For the most effective installation, use the following 
four-step process: 
1.  Set the OctoPOPIT switches. Refer to Section 
9.4.4 Setting the OctoPOPIT Switches. 
2.  Physically mount the OctoPOPIT in the 
enclosure. Refer to Section 9.4.5 Mounting 
OctoPOPITs,
 page 45. 
3.  Wire the OctoPOPIT. Refer to Section 9.4.6 
Wiring OctoPOPITs on page 45. 
4.  Wire the OctoPOPIT sensor loops. Refer to 
Section 9.4.7 OctoPOPIT Sensor Loops on page 
49. 
9.4.4  Setting the OctoPOPIT Switches 
The D8128D OctoPOPIT has two sets of DIP 
switches (Figure 19 on page 43). Use the DIP 
switches on the top of the unit (with the terminal strip 
along the left edge) to set the address for the 
OctoPOPIT. Use the DIP switches at the bottom of 
the unit to enable or disable individual points 
connected to the OctoPOPIT. 
Address Switches 
The switches on the D8128D OctoPOPIT set point 
assignments and line termination. These switches are 
easier to set before mounting the D8128D in the 
enclosure. 
Switches 1, 2, 3, and 4 assign the OctoPOPIT sensor 
loops to point numbers on the control panel. Table 14 
shows the OctoPOPIT switch settings for point 
assignments. 
Switch 5 sets line termination. Refer to Table 15
Table 14:  D8128D OctoPOPIT Switch Settings 
for D9412GV3 and D7412GV3 
 
ZONEX 1 
D8128D Address Switches 
ZONEX 2 
Points 9 to 
127 
1 2 3 4 5 
Points 129 
to 247 
9 to 16 
ON 
ON 
ON 
ON 
129 to 136 
17 to 24 
ON 
ON 
ON 
OFF 
137 to 144 
25 to 32 
ON 
ON 
OFF 
ON 
145 to 152 
33 to 40 
ON 
ON 
OFF 
OFF 
153 to 160 
41 to 48 
ON 
OFF 
ON 
ON 
161 to 168 
49 to 56 
ON 
OFF 
ON 
OFF 
169 to 176 
57 to 64 
ON 
OFF 
OFF 
ON 
177 to 184 
65 to 72 
ON 
OFF 
OFF 
OFF 
185 to 192 
73 to 80 
OFF 
ON 
ON 
ON 
193 to 200 
81 to 88 
OFF 
ON 
ON 
OFF 
201 to 208 
89 to 96 
OFF 
ON 
OFF 
ON 
209 to 216 
97 to 104 
OFF 
ON 
OFF 
OFF 
217 to 224 
105 to 112 
OFF  OFF 
ON 
ON 
225 to 232 
113 to 120 
OFF  OFF 
ON 
OFF 
233 to 240 
121 to 127 
OFF  OFF 
OFF 
ON 
241 to 247 
Line Termination Switch 
 
 
 
For the D8128D OctoPOPITs assigned to 
Points 121 to 127, 241, and 247, set Point 
Input Switch 8 to the OPEN position. 
D9412GV3 uses Points 9 to 127 on Zonex 
1 and Points 129 to 247 on Zonex 2. 
D7412GV3 uses Points 9 to 75 on Zonex 1 
only. 
 
 
Table 15:  Switch 5 Settings for Line 
Termination 
 
Is a D8125 POPEX 
Module connected? 
Switch 5 Setting(s) on 
D8128D OctoPOPIT(s) 
No 
Set Switch 5 of only one 
D8128D to ON 
Yes 
Set Switch 5 of all 
D8128Ds to OFF 
Point DIP Switches 
Each point connected to the D8128D is enabled by 
closing the respective DIP switch, or disabled by 
opening the DIP switch. For example, to disable a 
device connected to the P3 Terminal (Point 3), move 
DIP switch number 3 to the OPEN position.