TR21, TR22, TR23, AND TR24 WALL MODULES
62-0267—09
2
Fig. 1. Temperature vs. Resistance for Nonlinear Sensor.
Communications
All wall modules (except the TR21 and TR21-A models) have 
a L
ON
M
ARK®
 bus communications port. If needed, the jack 
plug must be removed in the field, and terminals 3 and 4 wired 
according to the installation instructions.
The recommended wire size for the L
ON
M
ARK®
 bus is Level 
IV, 22 AWG (0.34 sq.mm) plenum or non-plenum rated, 
non-shielded, twisted pair, solid conductor wire.
Fig. 2. Wall Module Features (TR23-F Shown).
BEFORE INSTALLATION
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can 
introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large inductive 
loads such as motors, line starters, lighting ballasts, 
and large power distribution panels.
Shielded cable is required in installations where these 
guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes  
and ordinances or as specified on installation wiring 
diagrams.
— Wall module wiring can be sized from 16 to 22 AWG 
(1.31 to 0.33 sq. mm) depending on the application.
— The maximum length of wire from a device to a wall 
module is 1000 ft. (305 m).
— Twisted pair wire is recommended for wire runs longer than 
100 ft. (30.5 m).
INSTALLATION
Mount the wall module on an inside wall approximately 54 in. 
(1372 mm) from the floor (or in the specified location) to allow 
exposure to the average zone temperature. Do not mount the 
wall module on an outside wall, on a wall containing water 
pipes, or near air ducts. Avoid locations that are exposed to 
discharge air from registers or radiation from lights, 
appliances, or the sun. See “Cover Disassembly” on page 3.
The wall module can be mounted on a wall, on a standard 
utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm 
wall outlet box (see Fig. 3). When mounting directly on a wall, 
use the type of screws appropriate for the wall material.
Fig. 3. Mounting on Standard Utility Conduit Box or 
60 mm Wall Outlet Box (TR23 Shown).
TEMPERATURE (DEGREES)
o
F
30
40
50
60
70
80
90
100 110
0
10
20
30
40
RESISTANCE (OHMS)
20K OHM AT 
77
o
F (25
o
C)
80K
70K
60K
50K
40K
30K
20K
10K
o
C
M5874A
M28125
FAN SWITCH, 3 OR 5 POSITION
DEPENDING ON MODEL
(TR22, TR23, AND TR24 MODELS ONLY)
LED (TR23 AND TR24 MODELS ONLY)
TEMPERATURE DIAL,
FAHRENHEIT DIAL SHOWN
(TR22 AND TR23 MODELS ONLY)
BYPASS (OVERRIDE) BUTTON
(TR23 AND TR24 MODELS ONLY)
LON CONNECTOR,
SHOWN WITH PROTECTIVE CAP IN PLACE
(NOT AVAILABLE ON TR21 AND TR21-A MODELS)
LOCKING TAB SLOT (X2)
60
70
80
M28126
STANDARD UTILITY CONDUIT BOX
SUBBASE
NO. 6 SCREW
60 mm WALL
OUTLET BOX
SUBBASE
3.5 mm SCREW
FRONT COVER
FRONT COVER