TR21, TR22, TR23, AND TR24 WALL MODULES
62-0267—09
4
Wiring and DIP switch settings:
See Table 1 to determine DIP switch positions and terminal usage for each controller.
Table 1. DIP Switch Settings and Terminal Connections.
Controller Model(s)
TR23-TR24 DIP Switch Settings
TR22-TR24 Terminal Connections
No fan switching from sensor
XL1O:
W7750, W7751, and W7752
Spyder: PUL, PVL
T7350: Use +/- offset knob 
only!
NOTE: These switch positions are the factory 
default settings for non-fan models.
Fan switching from sensor.
W7753
Spyder: PUL, PVL
XL5000:
Excel 600/500/100/80/50
• Used with TR23, TR24, 
TR22-F5, TR23-F3, and 
TR23-F5 models.
Any controller noted above.
For humidity models – TR21-H 
and TR23-H only!
M28128
DIP SWITCH S3
(TR23 AND TR24 ONLY.)
ON
SW1 SW2 SW3
DIP SWITCH S2
ON
SW1 SW2
DIP SWITCH
S1
ON
SW1 SW2
1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY.
1
DO NOT CHANGE THIS 
SWITCH POSITION.
1
11
10
9
8
7
6
5
4
3
2
12
GND
SENSOR
LON +
LON -
SETPT
LED
OVERRIDE
M28133
NOT USED ON TR24
NOT USED ON TR22
M28129
ON
SW1 SW2 SW3
DIP SWITCH S2
ON
SW1 SW2
DIP SWITCH
S1
ON
SW1 SW2
1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY.
1
DO NOT CHANGE THIS 
SWITCH POSITION.
DIP SWITCH S3
(TR23 and TR24 ONLY.)
1
11
10
9
8
7
6
5
4
3
2
12
GND
SENSOR
LON +
LON -
SETPT
LED
OVERRIDE
FA
N
M31112
NOT USED ON TR24
NOT USED ON TR22
M31110
DIP SWITCH S3
(TR23 and TR24 ONLY.)
ON
SW1 SW2 SW3
DIP SWITCH S2
ON
SW1 SW2
DIP SWITCH
S1
ON
SW1 SW2
1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY.
1
DO NOT CHANGE THIS 
SWITCH POSITION.
1
11
10
9
8
7
6
5
4
3
2
12
GND
SENSOR
LON +
LON -
SETPT
LED
FA
N
OVERRIDE
M31111
BYP
ASS RET
NOT USED
ON TR24
NOT USED ON TR22
M28132
0 TO 10 VDC
0 TO 5 VDC
4 TO 20 mA
DIP SWITCH S1
ON
SW1 SW2
ON
SW1 SW2
ON
SW1 SW2
1
11
10
9
8
7
6
5
4
3
2
12
M28137
HUM
24 V
A
C
REFER TO CONTROLLER SPECIFIC
WIRING ABOVE FOR TERMINAL
CONNECTIONS 1 THROUGH 10.