Honeywell TR22 Manual De Usuario

Descargar
Página de 8
TR21, TR22, TR23, AND TR24 WALL MODULES
62-0267—09
6
Fig. 7. Override pushbutton operation.
When Used With Excel 600/500/100/80/50 
Controllers:
The application engineer/programmer can program the 
override (bypass) and LED to operate in any manner desired. 
The override (bypass) input is a dry contact, normally open, 
momentary digital input when the wall module does not have a 
fan switch. When a fan speed switch (basically a series of 
resistances based on fan switch position) is present, the 
override button is an analog input. See Table 4 fo
resistances. 
When Used With T7350 Thermostat:
TR21, TR21-A, TR21-H, TR22, TR23, and TR24 are the 
models compatible with the T7350 thermostat. When using 
with the T7350 thermostat be sure to use the relative +/- offset 
knob only. The Celsius and Fahrenheit knobs will not work 
properly with the T7350 Thermostat.
TR22-F5, TR23-F3, and TR23-F5 Wall 
Module Fan Switch
With the switch in the far left position (Auto), the fan 
automatically runs at the speed determined by the controller 
temperature control algorithm. 
With the switch in the 0 position, the fan is off. Position 1 is fan 
speed 1, etc.
The wall module fan speed switch overrides the temperature 
control algorithm.
When Used With Excel 10 Controllers:
The Excel 10 Controllers (W7750, W7751, W7752, and 
W7753) can be programmed so that the fan speed switch and 
override button function the way that the application engineer/
programmer wants. See Table 7 for controller-programming 
resistances. Switch 1 on Dip Switch S2 adds 10k Ohms 
resistance when OPEN (for Excel 600-80 controllers) and 
removes it when CLOSED (for Excel 10 controllers). 
When Used With Excel 600/500/100/80/50 
Controllers:
Excel 600/500/100/80 Controllers can be programmed so that 
the fan speed switch and override button function the way that 
the application engineer/programmer wants. See Table 8 for 
controller-programming resistances. Switch 1 on Dip Switch 
S2 adds 10k Ohms resistance when OPEN (for Excel 600-80 
controllers) and removes it when CLOSED (for Excel 10 
controllers). 
Table 6. Wall Module Operation.
Pushbutton Held Down Controller Model
LED Status
0 to 1 second
No override
Off
1 to 4 seconds
Timed occupied
override
On
4 to 7 seconds
Unoccupied override Single blink per second
Longer than 7 seconds
No override
Off
not applicable
Continuous occupied
override
a
a
Remote function, which is generated from the network.
Two blinks per second
OVERRIDE
OCCUPIED
(LED ON)
UNOCCUPIED
(LED BLINK)
NOT ASSIGNED
(LED OFF)
RESET
M28145
PRESS FOR ONE
TO FOUR SECONDS
PRESS FOR FOUR
TO SEVEN SECONDS
PRESS FOR 
LESS THAN
ONE SECOND
PRESS FOR 
LESS THAN
ONE SECOND
PRESS FOR 
MORE THAN
SEVEN SECONDS
BYPASS
TIMEOUT
Table 7. Program Settings for Wall Modules with 
Fan Switch using Excel 10 Controllers.
For Switch Position
Resistance (Ohms)
Comment
Auto
1861 ±119
Left most position
0
2686 ±127
Fan Off position
1
3866 ±139
2
3041 ±130
3
4601 ±146
Right most position
Override button closed Closed circuit
Table 8. Program Settings for Wall Modules with 
Fan Switch using Excel 600/500/100/80 Controllers.
For Switch Position
Resistance (Ohms)
Comment
Auto
11.861K ±119
Left most position
0
12.686K ±127
Fan Off position
1
13.866K ±139
2
13.04K ±130
3
14.60K ±146
Right most position
Override button closed 10K ±100