INTROdUCTION
The  generator  revolving  field  (rotor)  is  driven  by  an 
air-cooled engine at about 3600 rpm.
The generator may be used to supply electrical power 
for the operation of 120 and/or 240 volts, 1-phase, 60 
Hz, AC loads.
ENgINE-gENERATOR dRIVE SYSTEM
The  generator  revolving  field  is  driven  by  an  air-
cooled, horizontal crankshaft engine. The generator is 
directly coupled to the engine crankshaft (see Figure 
1). Both the engine and generator rotor are driven at 
approximately 3600 rpm, to provide a 60 Hz AC out-
put.
THE AC gENERATOR
Figure  3-1  shows  the  major  components  of  the  AC 
generator.
ROTOR ASSEMbLY
The  2-pole  rotor  must  be  operated  at  3600  rpm  to 
supply  a  60  Hertz  AC  frequency. The  term  “2-pole” 
means the rotor has a single north magnetic pole and 
a single south magnetic pole. As the rotor rotates, its 
lines  of  magnetic  flux  cut  across  the  stator  assem-
bly  windings  and  a  voltage  is  induced  into  the  stator 
windings. The  rotor  shaft  mounts  a  positive  (+)  and 
a  negative  (-)  slip  ring,  with  the  positive  (+)  slip  ring 
nearest the rear bearing carrier (Figure 3-2). The rotor 
bearing is pressed onto the end of the rotor shaft. The  
tapered rotor shaft is mounted to a tapered crankshaft 
and is held in place with a single through bolt.
Page 9
STATOR
ENGINE
ENGINE
ADAPTOR
REAR BEARING
CARRIER
BRUSH HOLDER
ASSEMBLY
ROTOR
Figure 3-1. – AC Generator Exploded View