section 3
DescRiption & coMponents
The resulting direct current from the BCR is delivered 
to  the  12 VDC  receptacle,  via Wire  13A,  CB1,  and 
Wire  15A.   This  receptacle  allows  the  capability  to 
recharge  a  12  volt  DC  storage  battery  with  provided 
battery charge cables.
INSULATION RESISTANCE
The  insulation  resistance  of  stator  and  rotor  wind-
ings is a measurement of the integrity of the insulat-
ing  materials  that  separate  the  electrical  windings 
from  the  generator  steel  core. This  resistance  can 
degrade  over  time  or  due  to  such  contaminants  as 
dust,  dirt,  oil,  grease  and  especially  moisture.  In 
most  cases,  failures  of  stator  and  rotor  windings  is 
due to a breakdown in the insulation. In many cases, 
a  low  insulation  resistance  is  caused  by  moisture 
that collects while the generator is shut down. When 
problems  are  caused  by  moisture  buildup  on  the 
windings, they can usually be corrected by drying the 
windings. Cleaning and drying the windings can usu-
ally eliminate dirt and moisture built up in the genera-
tor windings.
THE MEgOHMMETER
GENERAL:
A megohmmeter, often called a “megger”, consists of 
a  meter  calibrated  in  megohms  and  a  power  supply. 
Use a power supply of 500 volts when testing stators 
or rotors. DO NOT APPLY VOLTAGE LONGER THAN 
ONE (1) SECOND.
TESTING STATOR INSULATION:
All  parts  that  might  be  damaged  by  the  high  meg-
ger  voltages  must  be  disconnected  before  testing. 
Isolate all stator leads (Figure 3-9) and connect all of 
the  stator  leads  together.  FOLLOW THE  MEGGER 
MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 500 volts. Connect one 
megger test lead to the junction of all stator leads, the 
other  test  lead  to  frame  ground  on  the  stator  can. 
Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators 
may be calculated using the following formula:
MINIMUM INSULATION 
 
GENERATOR RATED VOLTS 
RESISTANCE 
=  
__________________________  +1 
(in “Megohms”) 
 
1000
EXAMPLE:  generator  is  rated  at  120  volts  AC. 
divide “120” by “1000” to obtain “0.12”. Then add 
“1” to obtain “1.12” megohms. Minimum insulation 
resistance for a 120 VAC stator is 1.12 megohms.
If the stator insulation resistance is less than the cal-
culated minimum resistance, clean and dry the stator. 
Then, repeat the test. If resistance is still low, replace 
the stator.
Use  the  Megger  to  test  for  shorts  between  isolated 
windings as outlined “Stator Insulation Tests”.
Also  test  between  parallel  windings.  See  “Test 
Between Windings” on next page.
TESTING ROTOR INSULATION:
Apply a voltage of 500 volts across the rotor positive 
(+) slip ring (nearest the rotor bearing), and a clean 
frame ground (i.e. the rotor shaft). DO NOT EXCEED 
500  VOLTS  AND  DO  NOT  APPLY  VOLTAGE 
LONGER  THAN  1  SECOND.  FOLLOW  THE 
MEGGER  MANUFACTURER’S  INSTRUCTIONS 
CAREFULLY.
RotoR MiniMuM insulation Resistance: 
1.5 megohms
*
   caution: before attempting to measure 
insulation resistance, first disconnect and 
isolate all leads of the winding to be tested. 
electronic components, diodes, surge protec-
tors, relays, voltage Regulators, etc., can be 
destroyed if subjected to high megger volt-
ages.
HI-POT TESTER:
A  “Hi-Pot”  tester  is  shown  in  Figure  3-8. The  model 
shown  is  only  one  of  many  that  are  commercially 
available. The tester shown is equipped with a voltage 
selector switch that permits the power supply voltage 
to be selected. It also mounts a breakdown lamp that 
will illuminate to indicate an insulation breakdown dur-
ing the test.
Figure 3-8. – One Type of Hi-Pot Tester
STATOR INSULATION RESISTANCE TEST
GENERAL:
Units  with  air-cooled  engines  are  equipped  with  (a) 
center  tapped  AC  power  windings,  (b)  an  excitation 
Page 13