Guardian Technologies 4582 & 4987 Manual De Usuario

Descargar
Página de 90
00.00
C.B.
20/30A
Figure 6-8. – 20/30 Amp Breaker Test Points
TEST 3 - TEST EXCITATION CIRCUIT bREAkER
PROCEDURE:
1. With the generator shut down for at least two minutes, locate
the Excitation Circuit Breaker in the control panel. Disconnect
wires from the breaker, to prevent interaction.
2. Set a volt meter to measure resistance.
3. Connect the VOM test probes across the circuit breaker termi-
nals. The meter should read CONTINUITY.
RESULTS:
1. If circuit breaker tests bad (meter reads “OPEN”) then proceed
to Test 4 and replace the breaker after completing Test 4.
2. If circuit breaker is good, go on to Test 4.
2
162
00.00
Figure 6-9. - Testing Excitation Circuit Breaker
TEST 4 - FIXEd EXCITATION TEST/ 
ROTOR AMP dRAW
PROCEDURE:
*NOTE:  If  the  generator  is  not  producing  AC 
Power,  loss  of  governor  control  may  occur  caus-
ing  an  overspeed  or  extremely  high  RPM  condi-
tion.  If  this  condition  occurs  manually  control 
throttle (60Hz /3600 RPM) to perform test.
1. Unplug the six pin connector at the Voltage Regulator.
2. Disconnect Wire 14 from the Resistor (R1).
3. Connect a jumper wire between the removed end of Wire 14
and Wire 4 where it is soldered at the Diode (D1). See Figure
6-10.
R1
D2
4
14
14
4
D2
4
14
WIRE 14 
REMOVED
JUMPER LEAD
14
4
R1
 
Figure 6-10. – Jumper Lead From Wire 14 to Diode
4. Set voltmeter to measure AC voltage
5. Disconnect Wire 2 from the Excitation Circuit Breaker and con-
nect one meter test lead to it. Connect the other meter test lead
to Wire 6 located in the six pin connector previously removed
from the Voltage Regulator. Be careful not to damage the pin
connectors with the test leads. See Figure 6-11.
6. Set Idle control switch to OFF.
7. Start the generator.
8.  Measure  the  output  voltage  across Wire  2  and Wire  6  and
record the results.
AC Voltage across Wires 2 and 6 = _____________
section 6
Diagnostic tests
Page 38