3com MS40-717X Manual De Usuario

Descargar
Página de 16
F-26748-6
© Copyright 2010 Schneider Electric All Rights Reserved.
5
MS40-7171
Brown         
Light Blue         
L1
L2
240 Vac
GRD
Green/Yellow        
Yellow/Black       
Gray       
AI 
COM 
2 to 10 Vdc
+
-
Control 
Signal
1
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue       
AO 
1  Unused conduit port must remain plugged with a water 
tight pipe plug as shipped from factory to maintain 
NEMA Type 4 or IP56 rating.
2  Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs 
from current models. See Table 4 on page 14. Consult 
label on product to confirm wiring codes.
3  Keep AI, COM and AO wiring less than 30 meters 
length to meet CE requirements.
2
3
Figure-3 Typical MS40-7171 2 to 10 Vdc Wiring Diagram.
MS40-7171
Brown        
Light Blue         
L1
L2
240 Vac
GRD
Green/Yellow        
Yellow/Black       
Gray      
AI 
COM 
4 to 20 mA
+
-
500 Ohm 
1
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue       
AO 
Control
Signal
1  Unused conduit port must remain plugged with a water 
tight pipe plug as shipped from factory to maintain 
NEMA Type 4 or IP56 rating.
2  Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs 
from current models. See Table 4 on page 14. Consult 
label on product to confirm wiring codes.
3  Keep AI, COM and AO wiring less than 30 meters 
length to meet CE requirements.
2
3
Figure-4 Typical MS40-7171 4 to 20 mA Wiring Diagram.
MS40-7173
Red           
Black          
24H (DC+)
24G (DC-)
24 Vac or 22-30 Vdc
GRD
Green/Yellow          
Yellow/Black        
Gray         
AI 
COM 
+
-
2 to 10 Vdc
1
Transformer
Control
Signal 
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue       
AO 
1  Unused conduit port must remain plugged with a water 
tight pipe plug as shipped from factory to maintain 
NEMA Type 4 or IP56 rating.
2  Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs 
from current models. See Table 4 on page 14. Consult 
label on product to confirm wiring codes.
3  Keep AI, COM and AO wiring less than 30 meters 
length to meet CE requirements.
2
3
Figure-5 Typical MS40-7173 2 to 10 Vdc Wiring Diagram.