MICROMASTER Applications Handbook
7.5.4
Key Parameter settings
Table 7-5
Key Parameters. Material Handling Operation
Number Value
Meaning
P1120
0.3
Ramp up
P1121
0.3
Ramp down
P0003
003
Allows all parameters to be adjusted and set.
P1082
100
Maximum Output Frequency. This wide speed range is possible
because torque requirements are not excessive at high speed.
because torque requirements are not excessive at high speed.
P2000
100
Reference Frequency. Used for analog, serial I/O etc. 0-10 V now
corresponds to 0-100 Hz
corresponds to 0-100 Hz
P0701 2
Run
left
P0702 1
Run
right
P0703 29
External
Trip
P0731
52.3
Output Relay 1 Brake control. Here the brake control operates
immediately as P1216 and P1217 are set to 0.
immediately as P1216 and P1217 are set to 0.
P1215
1
Enable brake control function
P1216
0
Brake release time
P1217
0
Brake stop time
P1310
0
Continuous boost. In this application starting boost (P1312) proved
more useful than continuous boost.
more useful than continuous boost.
P1312 100
Starting
boost
P0300-
P0311
P0311
***
Settings to suit motor