42
MICROMASTER Applications Handbook
7.4.4
Key Parameter Settings
Table 7-4
Key Parameters. Conveyor Application
Number Value Meaning
P1120
0.6
Ramp up
P1121
0.6
Ramp down. Fast ramping possible with these settings
P1000
003
Fixed frequency operation
P0003
3
Allows all parameters to be adjusted and set.
P1082
110
Maximum Output Frequency. High speed operation possible in certain
circumstances.
circumstances.
P1060
0.3
Jog (alternative) ramp up rate
P1061
0.3
Jog (alternative) ramp down rate
P1001
40
Fixed frequency 1
P1002
45
Fixed frequency 2
P0701
16
Run at fixed frequency 1
P0702
16
Run at fixed frequency 2
P1124
16722.2
Use jog ramp times BiCo Function
P0703
99
Enable BiCo function
P0300-
P0311
P0311
***
Settings to suit motor
By setting P0701 and P0702 to 16, the drive starts and runs to the selected
frequency.
frequency.