Guardian Technologies 5308 Manual De Usuario
00.00
C.B.
20/30A
Figure 6-8. – 20/30 Amp Breaker Test Points
TEST 3 - TEST EXCITATION CIRCUIT bREAkER
PROCEDURE:
1. With the generator shut down for at least two minutes, locate
1. With the generator shut down for at least two minutes, locate
the Excitation Circuit Breaker in the control panel. Disconnect
wires from the breaker, to prevent interaction.
wires from the breaker, to prevent interaction.
2. Set a volt meter to measure resistance.
3. Connect the VOM test probes across the circuit breaker termi-
nals. The meter should read CONTINUITY.
RESULTS:
1. If circuit breaker tests bad (meter reads “OPEN”) then proceed
1. If circuit breaker tests bad (meter reads “OPEN”) then proceed
to Test 4 and replace the breaker after completing Test 4.
2. If circuit breaker is good, go on to Test 4.
2
162
00.00
Figure 6-9. - Testing Excitation Circuit Breaker
TEST 4 - FIXEd EXCITATION TEST/
ROTOR AMP dRAW
PROCEDURE:
*NOTE: If the generator is not producing AC
*NOTE: If the generator is not producing AC
Power, loss of governor control may occur caus-
ing an overspeed or extremely high RPM condi-
tion. If this condition occurs manually control
throttle (60Hz /3600 RPM) to perform test.
1. Unplug the six pin connector at the Voltage Regulator.
1. Unplug the six pin connector at the Voltage Regulator.
2. Disconnect Wire 14 from the Resistor (R1).
3. Connect a jumper wire between the removed end of Wire 14
and Wire 4 where it is soldered at the Diode (D1). See Figure
6-10.
6-10.
R1
D2
4
14
14
4
D2
4
14
WIRE 14
REMOVED
JUMPER LEAD
14
4
R1
Figure 6-10. – Jumper Lead From Wire 14 to Diode
4. Set voltmeter to measure AC voltage
5. Disconnect Wire 2 from the Excitation Circuit Breaker and con-
nect one meter test lead to it. Connect the other meter test lead
to Wire 6 located in the six pin connector previously removed
from the Voltage Regulator. Be careful not to damage the pin
connectors with the test leads. See Figure 6-11.
to Wire 6 located in the six pin connector previously removed
from the Voltage Regulator. Be careful not to damage the pin
connectors with the test leads. See Figure 6-11.
6. Set Idle control switch to OFF.
7. Start the generator.
8. Measure the output voltage across Wire 2 and Wire 6 and
record the results.
AC Voltage across Wires 2 and 6 = _____________
section 6
Diagnostic tests
Diagnostic tests