section 2
MeasuRing electRicitY
engine  speed  governor.  For  models  rated  60  Hertz, 
the governor is generally set to maintain a no-load fre-
quency of about 62 Hertz with a corresponding output 
voltage  of  about  124  volts  AC  line-to-neutral.  Engine 
speed  and  frequency  at  no-load  are  set  slightly  high 
to prevent excessive rpm and frequency droop under 
heavy electrical loading.
MEASURINg CURRENT
CLAMP-ON:
To  read  the  current  flow,  in  AMPERES,  a  clamp-on 
ammeter  may  be  used. This  type  of  meter  indicates 
current  flow  through  a  conductor  by  measuring  the 
strength  of  the  magnetic  field  around  that  conductor. 
The  meter  consists  essentially  of  a  current  trans-
former with a split core and a rectifier type instrument 
connected  to  the  secondary. The  primary  of  the  cur-
rent  transformer  is  the  conductor  through  which  the 
current  to  be  measured  flows. The  split  core  allows 
the  instrument  to  be  clamped  around  the  conductor 
without disconnecting it.
Current  flowing  through  a  conductor  may  be  mea-
sured  safely  and  easily.  A  line-splitter  can  be  used 
to  measure  current  in  a  cord  without  separating  the 
conductors.
Figure 2-2. – Clamp-On Ammeter
Figure 2-3. – A Line-Splitter
NOTE:  If  the  physical  size  of  the  conductor  or 
ammeter  capacity  does  not  permit  all  lines  to  be 
measured  simultaneously,  measure  current  flow 
in  each  individual  line. Then,  add  the  individual 
readings.
IN-LINE:
Alternatively,  to  read  the  current  flow  in  AMPERES, 
an  in-line  ammeter  may  be  used.  Most  Digital Volt 
Ohm  Meters  (VOM)  will  have  the  capability  to  mea-
sure amperes.
This usually requires the positive meter test lead to be 
connected to the correct amperes plug, and the meter 
to be set to the amperes position. Once the meter is 
properly set up to measure amperes the circuit being 
measured  must  be  physically  broken. The  meter  will 
be in-line or in series with the component being mea-
sured.
In  Figure  2-4  the  control  wire  to  a  relay  has  been 
removed. The  meter  is  used  to  connect  and  supply 
voltage  to  the  relay  to  energize  it  and  measure  the 
amperes going to it. 
1.00 
A
BATTERY
+
-
RELAY
Figure 2-4. – A VOM as an In-line meter
MEASURINg RESISTANCE
The  volt-ohm-milliammeter  may  be  used  to  measure 
the  resistance  in  a  circuit.  Resistance  values  can  be 
very valuable when testing coils or windings, such as 
the Stator and Rotor windings.
When  testing  Stator  windings,  keep  in  mind  that  the 
resistance of these windings is very low. Some meters 
are not capable of reading such a low resistance and 
will simply read CONTINUITY.
If  proper  procedures  are  used,  the  following  condi-
tions can be detected using a VOM:
•  A “short-to-ground” condition in any Stator or Rotor 
winding.
•  Shorting  together  of  any  two  parallel  Stator  wind-
ings.
•  Shorting  together  of  any  two  isolated  Stator  wind-
ings.
•  An open condition in any Stator or Rotor winding.
Page 7