Configuring the Power System for Operation 
 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
4-7
 
Example 1 
Reconfiguring System Alarms 
In general reconfiguring system alarms requires the following: 
• 
Changing the urgency (Disabled, Relay Only, Urgent or 
Non Urgent) 
• 
Setting the alarm thresholds and recognition times 
For example, to reconfigure an alarm, follow the steps below. 
From the DCTools System Summary (Home) screen, click 
the Alarms hotlink.  The Alarm Table screen is then 
displayed. 
To change the urgency of an alarm, double-click on the 
Urgency for that alarm, then click the 
 button and select 
the new urgency from the popup list. 
To change alarm thresholds and recognition times, click 
the   button to the left of Alarm Configuration at the 
bottom of the Alarm Table screen and change the settings 
as required.