Configuring the Power System for Operation
Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.
IPN 997-00012-41D December 2006
4-7
Example 1
Reconfiguring System Alarms
In general reconfiguring system alarms requires the following:
•
Changing the urgency (Disabled, Relay Only, Urgent or
Non Urgent)
Non Urgent)
•
Setting the alarm thresholds and recognition times
For example, to reconfigure an alarm, follow the steps below.
1
From the DCTools System Summary (Home) screen, click
the Alarms hotlink. The Alarm Table screen is then
displayed.
the Alarms hotlink. The Alarm Table screen is then
displayed.
2
To change the urgency of an alarm, double-click on the
Urgency for that alarm, then click the
Urgency for that alarm, then click the
button and select
the new urgency from the popup list.
3
To change alarm thresholds and recognition times, click
the button to the left of Alarm Configuration at the
bottom of the Alarm Table screen and change the settings
as required.
the button to the left of Alarm Configuration at the
bottom of the Alarm Table screen and change the settings
as required.