System Operation
312779E
99
Solvent Push Feature
The Solvent Push feature enables the user to save 
some mixed material by pushing it out to the gun with 
solvent. The quantity saved is 50% of the potlife volume 
entered in Advanced Setup Screen 1 on page 39. If 
there are 2 guns, the smaller potlife volume is used.
Solvent Push requires an accessory solvent meter (MS). 
Order Graco Part No. 280555 S3000 Solvent Meter Kit. 
See manual 308778.
1.
See F
IG
. 108. Install the solvent meter (MS) on the 
side of the fluid station, as explained in the ProMix 
2KS Installation Manual.
2.
To enable Solvent Push, select “Solvent” or “3rd 
Valve,” as desired. SeOption Screen 2, page 37.
NOTE: If you are using a 3rd purge valve instead of the 
solvent purge valve to run the Solvent Push feature, 
connect the solvent supply line from the solvent meter to 
the inlet of the 3rd purge valve.
3.
Press and hold the Mix  
 key for 5 seconds 
to turn on Solvent Push. The green Mix LED will 
light and the Recipe LED will blink. The system will 
close the Dose Valves (DVA, DVB) and open the 
Solvent Purge Valve (SPV).
4.
The system will dispense solvent to push the mixed 
material out to the gun. The Booth Control display 
alternately shows dashes and the percent remaining 
(0-99%) of the 50% of the potlife volume.
NOTE: To manually interrupt Solvent Push, press the 
Standby 
 key. The Solvent Purge Valve (SPV) or 
3rd purge valve will close. To re-enter Solvent Push, 
press the Mix  
 key. 
5.
When the total solvent dispensed exceeds 50% of 
the potlife volume, the system will go into Standby 
 mode. 
6.
Perform a manual purge or recipe change to purge 
the remaining mixed material. This will clear the sys-
tem out of Solvent Push, allowing you to resume 
Mix mode. 
NOTE: Once the system senses that solvent exceeds 
50% of potlife volume, attempts to re-enter Solvent 
Push will cause an Overdose_A/B Alarm (E-5, E-6).
F
IG
. 108. Solvent Push Setup
DVB is closed
MS
SPV is open
DVA is closed
TI12556b
SMC
SS
Key:
DVA Component A Dose Valve
DVB Component B Dose Valve
MS
Solvent Meter (required)
SPV Solvent Purge Valve
APV Air Purge Valve
SMC Solvent Meter Cable
SS
Solvent Supply Line