mA output
Primary variable
Mass flow
LRV
–200.00000 g/s
Automatically reset when 
primary variable is reset.
URV
200.00000 g/s
Automatically reset when 
primary variable is reset.
AO cutoff
0.00000 g/s
AO added damping
0.00000 sec
0 – 440 seconds
Fault action
Downscale
AO fault level – downscale
2.0 mA
1.0 – 3.6 mA
AO fault level – upscale
22 mA
21.0 – 24.0 mA
Last measured value timeout
0.00 sec
Display
Update period
200 milliseconds
100 – 10,000 
milliseconds
Variable 1
Mass flow rate
Variable 2
Mass total
Variable 3
Volume flow rate
Variable 4
Volume total
Variable 5
Density
Variable 6
Temperature
Variable 7
Drive gain
Variable 8–15
None
Alarm menu
Enabled
Offline password
1234
Auto scroll
Disabled
Auto scroll rate
10 sec
Table A-1
Transmitter default values and ranges continued
Type
Setting
Default
Range
Comments