Emerson 2200S Manuel D’Utilisation

Page de 158
Configuration and Use Manual
27
Getting Ready to Configure
Op
eratio
n
App
e
ndi
ces
Mai
n
tenan
c
e and
 T
roub
le
sh
oo
tin
g
Com
m
is
si
on
in
g
Figure 3-1 illustrates the mA measurement point options. As shown:
If your installation does not include the Micro Motion adapter-barrier, always use 12–20 mA. .
If your installation does include the Micro Motion adapter-barrier, be sure you know the 
location of the measurement device and set the mA measurement point appropriately:
-
If the mA measurement device is between the transmitter and the adapter-barrier, use 
12–20 mA.
-
If the mA measurement device is between the adapter-barrier and the host, use 4–20 mA.
If you don’t know how to set the mA measurement point, specify Don’t Know. The 
Communicator and ProLink II will display data for both output scales. 
Figure 3-1
mA measurement point options
3.4.2
Converting between mA output scales
Equations for converting between mA output scales are shown in Table 3-1.
Table 3-1
mA output scale conversion equations
Conversion
Equation
12–20 mA to 4–20 mA
• X = value on the 4–20 mA scale
• Y = value on the 12–20 mA scale
4–20 mA to 12–20 mA
• X = value on the 4–20 mA scale
• Y = value on the 12–20 mA scale
12–20 mA
12–20 mA
4–20 mA
Micro Motion adapter-barrier
DCS
DCS
X
Y
10
(
) 2
×
=
Y
X
2
----
10
+
=