Emerson Process Management 2400S Manuel D’Utilisation
Configuration and Use Manual
133
Troubleshooting
Meas
ure
m
ent P
e
rf
ormance
Defaults
T
rou
b
b
le
s
ho
oti
n
oti
n
g
Compensa
tion
Erratic non-zero flow rate under
no-flow conditions
no-flow conditions
Leaking valve or seal
• Check pipeline.
Slug flow
• See Section 11.14.
Plugged flow tube
• Check drive gain and tube frequency.
Purge the flow tubes.
Incorrect sensor orientation
• Sensor orientation must be
appropriate to process fluid. See the
installation manual for your sensor.
installation manual for your sensor.
Wiring problem
• Check the sensor circuitry. See
Vibration in pipeline at rate close to
sensor tube frequency
sensor tube frequency
• Check environment and remove
source of vibration.
Damping value too low
• Check configuration. See Section 8.4.
Mounting stress on sensor
• Check sensor mounting. Ensure:
- Sensor is not being used to support
pipe.
- Sensor is not being used to correct
pipe misalignment.
- Sensor is not too heavy for pipe.
Sensor cross-talk
• Check environment for sensor with
similar (±0.5 Hz) tube frequency.
Erratic non-zero flow rate when flow
is steady
is steady
Slug flow
• See Section 11.14.
Damping value too low
• Check configuration. See Section 8.4.
Plugged flow tube
• Check drive gain and tube frequency.
Purge the flow tubes.
Excessive or erratic drive gain
• See Section 11.20.3
Output wiring problem
• Verify wiring between transmitter and
receiving device. See the installation
manual for your transmitter.
manual for your transmitter.
Problem with receiving device
• Test with another receiving device.
Wiring problem
• Check the sensor circuitry. See
Inaccurate flow rate
Bad flow calibration factor
• Verify characterization. See
Inappropriate measurement unit
• Check configuration. See
Bad sensor zero
• Rezero the flowmeter or restore the
factory zero or prior zero. See
Section 10.5.
Section 10.5.
Bad density calibration factors
• Verify characterization. See
Bad flowmeter grounding
• See Section 11.7.3.
Slug flow
• See Section 11.14.
Wiring problem
• Check the sensor circuitry. See
Table 11-3
Process variables problems and remedies continued
Symptom
Cause
Suggested remedy