Installation of Leak Detection System Cable
1. Attach the leak detection cable to the LT460 module.
2. Activate module and test detection cable. (Touch detection cable 
with a clean moist cloth or paper towel.) Dry detection cable to 
remove the alarm condition. (A hair dryer can be used to speed up 
the drying.)
Note: Do not try to saturate the detection cable for testing! It only 
requires a small amount of water to alarm. The detection cable will 
have to dry for the alarm condition to clear.
3. Once the cable passes the test, lay it in the pattern desired.
DETECTION CABLE PLACEMENT PRECAUTIONS
• Do not use detection cable that is damaged or dirty—for 
example, from plaster, spackle or construction debris.
• Detection cable should not be dragged through contaminants 
(dirty or greasy areas). Floor must be clean for the detection 
cable to function properly and for the hold-down clips to 
adhere to the floor surface.
• Careful consideration should be taken to place detection cable 
out of the direct discharge airflow path of environmental 
equipment. This type of equipment can discharge moisture 
into the airflow. Place cable six feet from discharge to avoid 
nuisance alarms during humidification.
• Tools or heavy objects can do permanent damage when 
dropped, rolled, or set on the detection cable. Avoid foot traffic 
on the detection cable as well.
• Do not use any type of adhesive tapes to secure the detection 
cable.
• Do not allow soldering or welding near the detection cable 
without providing protection from heat or contaminants. (Also 
avoid installing the detection cable in or near these type of 
areas.)
• Mild dishwashing liquid can be used to clean the detection 
cable of many contaminants.