Alarm Retest Delay (SS3)
SS3 selects the alarm retest delay, the setting in which an alarm is 
latched and retested every hour.
OFF = Non-latching (default)
ON = Latching-retest each hour
The factory default is OFF=Non-latching. If SS3=ON and a leak is 
detected, the alarm condition is latched, the sensor goes into a “sleep” 
mode and power to the leak detection cable is discontinued. After one 
hour, the sensor will automatically retest if the leak is still present. If 
the leak has cleared itself, the sensor deactivates the alarm, resets 
itself and resumes normal operation; if the leak is still present, the 
alarm condition remains activated and the sensor goes to “sleep” and 
retests in another hour. This procedure will repeat indefinitely until 
the leak is cleared or until the alarm is manually reset. 
A manual reset can be initiated at any time. If the leak condition has 
not yet cleared, the sensor re-alarms after the selected leak detect fil-
ter delay; if the leak has cleared, the sensor deactivates the alarm and 
resets itself. SS3 is disabled if SS2=ON.
The factory default settings of SS2=OFF and SS3=OFF place the 
sensor in a non-latching, continuous retest mode. The sensor does not 
go to “sleep” after detecting a leak—instead, it continually checks to 
determine whether the leak condition has cleared itself. Alarms auto-
matically reset when the leak condition clears. Initiating a manual 
reset will cause the sensor to trigger the alarm again after the selected 
leak detect filter delay. The leak detect cable remains powered at all 
times.
SS4 is not used.
SS1
SS2
SS3
SS4
MODE
OFF
OFF
OFF
(not 
used)
Non-latching, 10-second filter delay 
(factory default)
ON
OFF
OFF
(not 
used)
Non-latching, 2-minute filter delay
OFF
ON
(not 
used)
Latching, 10-second filter delay
ON
ON
(not 
used)
Latching, 2-minute filter delay
OFF
OFF
ON
(not 
used)
1-hour latch/retest, 10-second filter delay
ON
OFF
ON
(not 
used)
1-hour latch/retest, 2-minute filter delay