Emerson 460 Manuel D’Utilisation

Page de 16
5
Configuration Switch Settings
A four-position DIP switch is used to 
select two alarm (filter) delays and 
three mutually exclusive alarm 
modes. The switches are located 
next to the wiring termination 
blocks.
Leak Detect Filter Delay(SS1)
SS1 selects the leak detect filter 
delay, the interval for which a leak 
condition must be continuously 
detected before an alarm is 
triggered: 
OFF = 10 seconds (default)
ON = 2 minutes
This feature is useful for eliminat-
ing nuisance alarms. SS1 works 
independently of the settings of SS2 
and SS3. While the alarm delay is selectable (factory default is 
OFF=10 seconds), the cable fault delay is preset at approximately 
2 seconds.
Latching or Non-Latching Alarms (SS2)
SS2 selects latching or non-latching alarms, the setting in which an 
alarm will latch ON until manually reset:
OFF = Non-latching (default)
ON = Latching
The factory default is OFF=Non-latching. If the sensor is in latching 
mode (ON=Latching) and the leak condition clears itself in the 
interim, a manual reset is required. While the alarm is latched, the 
sensor goes into a “sleep” mode and power to the leak detection cable 
is discontinued. De-powering the cable prevents damage to the cable 
should it be in contact with the conductive liquid for an extended 
duration. After a manual reset, the sensor resumes its normal opera-
tion, continuously checking for leaks. If the leak condition has not yet 
cleared but the sensor is manually reset, the sensor will re-alarm after 
the appropriate leak detect filter delay. SS2 in the ON position will 
disable the operation of SS3.
Switch Settings
OFF
ON
S1
1. Leak Detect Filter
10sec 2min
2. Alarm Latch
No
Yes
3. Alarm Retest Delay
No
1hr
4. Not Used
Contacts
Rating:
24V,3A
CONNECT ENCLOSURE TO EARTH GROUND
TB3-3
TB3-2
TB3-1
TB2-3
TB2-2
TB2-1
TB1-2
TB1-1
Contacts
Rating:
24V,3A
24V 
50/60Hz
0.12A
2
1
N.C.
C
N.O.
N.C.
C
N.O.
ALL CIRCUITS: CLASS 2
Contacts shown in POWERED, NON-ALARM state