Omron FQM1-MMA21 Manuel D’Utilisation

Page de 414
252
Error Processing
Section 9-2
9-2-7
Memory Error Check
9-2-8
Program Error Check
Memory error occurred
ON
OFF
No
Yes
Flash Memory Error Flag 
(A403.10) ON?
The internal flash memory's rewrite limit has 
been exceeded. Replace the Module.
Was power 
interrupted while backing 
up memory with the CX-
Programmer?
The power supply was turned OFF during a 
memory backup. Transfer the data again.
There was a hardware failure in the internal 
memory. Replace the Module.
ON
OFF
ON
OFF
Program error occurred
Task Error Flag 
(A405.12) ON?
The called task does not exist. Check the 
MSKS instruction that enables the interrupt 
task with the corresponding task number.
There isn't an END instruciton in the 
program. Add an END instruction.
No END Error Flag 
(A405.11) ON?
Turn the power supply OFF and ON again.