Omron FQM1-MMA21 Manuel D’Utilisation

Page de 414
253
Error Processing
Section 9-2
9-2-9
Cycle Time Overrun Error Check
9-2-10 System Setup Error Check
Not cause
of error
The program execution time exceeded the 
watch cycle time. Increase the watch cycle 
time setting in the System Setup.
Yes
No
Yes
No
No
Yes
Cycle Time Overrun Error
occurred
Is the assumed
cycle time less than the
watch cycle time set in the
System Setup?
Are interrupts
being used?
Is the Max.
Interrupt Processing Time
setting OK?
It is possible that the error occurred 
because the interrupt task execution time 
was too long.
It is possible that the error occurred 
because two or more interrupt tasks were 
executed. Check how often interrupt tasks 
are executed.
There may be an error in the program. 
Check all tasks, particularly instructions that 
control loops ,such as the JMP instruction.
#0154 hex (340)
Other value
Set the proecessing mode correctly.
System Setup Error occurred
What is in
the System Setup Error 
Location (A406)?
A communications error may have occurred
during the transfer from the CX-Programmer.
Transfer the System Setup again.