Herrmidifier Co 6000 Manuel D’Utilisation

Page de 24
Problem / Symptom 
Probable Cause 
Reason - Correction 
Dead short between electrodes. 
 
Replace the steam cylinder. Check 
resistance between electrodes with 
power “off” 
 
Restricted or blocked drain. 
Clean and inspect drain system. 
Restricted fill system 
Clean and inspect the fill system.  
Check for restriction or loss of supply 
pressure. 
Incoming water conductivity is outside 
the range of normal circuit board 
settings.   
Consult the factory for options. 
Overcurrent 
The alarm condition occurs when an 
overcurrent situation (>138% of rated 
current) has occurred and the 
humidifier has shut down to prevent 
any damage. This alarm indicates that 
there has been a significant reduction 
in resistance between the main legs of 
the supply power and the humidifier 
has been shut down to prevent 
damage and should be serviced 
before it is restarted. Overcurrent LED 
CR 17 (Figure 12) is illuminated. 
Check amp draw to unit during start-
up.  If amp draw greatly exceeds rated 
amp draw, the drain threshold pot, 
labeled “% adj.” (R18), must be 
increased 2% to increase the 
frequency and duration of drains to 
reduce the conductivity inside the 
cylinder.  
Manually drain the unit and restart. 
End of cylinder life – Cylinder life is 
typically between 500 and 2000 hours, 
depending on incoming water supply.  
(See unit operation section for typical 
cylinder life expectancy chart on Pg. 
5). 
For emergency use, you may restart 
the humidifier with the capacity 
setpoint, R39, at a lower level to allow 
operation until a replacement steam 
cylinder can be obtained.  To clear the 
fault, turn the main disconnect to the 
unit “off” and then back “on”. 
If incoming water supply is less than 
100 micromho, the unit may not be 
able to pass the rated current through 
the water.  
See – NON-FAULT ACTIVATED 
PROBLEMS GUIDE 
– “Unit fills to the 
cylinder full condition and remains 
cold” 
End of Cylinder  
This alarm condition occurs if the 
humidifier is unable to reach full output 
over a 6-hour timeframe.  It is 
constantly switching between “fill” and 
“cylinder full” modes.  This alarm 
indicates a need to change the 
cylinder that the water supply is low in 
conductivity that the water supply is 
low in conductivity, or that a foaming 
condition exists: 
 
Foaming condition exists.   
Flush and fill the steam cylinder 
several times and restart.  If it persists, 
you must filter or treat the water to 
remove the foaming agent.  See circuit 
board settings on previous page if 
supply water is softened. See NON – 
FAULT ACTIVATED PROBLEMS 
GUIDE
 – “Water foaming inside the 
cylinder” 
Loss of or restricted water supply 
Check fill system. 
Leaking drain system. 
Check drain system. 
Defective drain valve. 
Repair and replace as required. 
Fill System Fault 
This alarm condition occurs when the 
fill valve has been energized for a 6-
hour timeframe.  The humidifier has 
been shutdown to prevent any 
damage. 
Defective fill valve. 
Repair and replace as required. 
Unit Detected Faults: (Red “Service” Light On)
NOTE: The three fault conditions outlined above will cause the humidifier to shut down and the service light on the
front of the unit to illuminate.  To clear these faults, the main power must be turned “off” and back “on” again.
 
 
 
14