SECTION II UNIT OPERATION 
 
 Basic Operation 
 
Controlled humidification requires a very precise control 
system. The 6000 utilizes a solid state control to monitor 
performance and maintain humidity. The humidifier 
evaluates the operation and alerts the operator to 
problem conditions and prevents undesirable operation. 
 
On initial start-up or a call for humidity, the humidifier will 
attempt to fill to its full load amp rating. The unit will not 
necessarily have a full cylinder of water.
 Water level 
depends on the conductivity of the water. The more 
conductive the water, the more current that can be 
passed through the same volume of water. 
 
If the water is not conductive enough to allow the unit to 
reach full load amps (full capacity) on the initial fill; the 
cylinder full light will indicate a full cylinder condition. The 
unit will operate in this mode with repetitive fill and boil 
cycles unit the unit has concentrated enough minerals in 
the water to reach the rated amp level. 
 
Once full load amp (FLA) has been reached, the fill valve 
will shut off. The unit will now compare the rate of 
change of amp draw to a time cycle. 
 
If the water in the cylinder is mineral laden and hence 
very conductive, a dram cycle will be initiated. 
 
 
 
 
After the dram cycle and or the time cycle is completed, 
the unit will refill and start the process over. 
 
These cycles will repeat until: 
•  The call for humidity is removed. 
•  The cylinder is used up. 
•  A fault condition occurs. 
 
On initial start-up, if the water is not conductive enough 
for the unit to reach FLA, the water will stop filling when 
the water reaches the cylinder f4U electrode. Once the 
unit has entered a cylinder full condition it  will operate 
with fill and boil  cycles only. By eliminating the dram 
cycle, the water conductivity will be increased by 
producing pure steam and letting the minerals behind. 
The increased mineral levels will raise the conductivity 
allowing the humidifier to draw sufficient amperage to 
achieve FLA. Normal operation will then commence. 
 
As the electrodes in the cylinder are coated with 
minerals, the water level will slowly increase to the 
cylinder full level. Concentration will no longer allow the 
unit to reach FLA.  After a period of time, the cylinder will 
display the red “Service" light indicating the need to 
change the cylinder. 
 