NOTE: Provisions must be made to prevent the condensate from entering the water heater. 
Without proper drainage or disposal condensate will damage the heat exchanger.
Horizontal Venting with a
Condensate Collector
Horizontal Venting without a
Condensate Collector
Condensate
Trap
Vertical Venting
(condensate collector required)
Maximum Height
5 feet
3 in
min
3 in
min
3 in
min
Regions of cold climate will create
more condensate in the vent
system. A condensate collector is
recommended in cold climates.
If more than one elbow is used
in the vertical section you must
use a condensate collector.
Rinnai America
FF  Models
I N S TA L L E R ’ S  I N S TA L L AT I O N  I N S T R U C T I O N S
Venting
Condensate
Condensate  formation  can  occur  in  Category  III  direct  vent  appliances.
•  Vertical terminations must incorporate a condensate drain and trap as close as possible to 
the  appliance.
•  The condensate trap must contain a minimum of 3" of water.
•  Dispose of condensate per local codes.
•  Slope horizontal venting 1/4 inch per foot either towards the heater with a condensate 
collector  or  towards  the  exhaust  terminal.