Nordyne SERIES M1B Manuel D’Utilisation

Page de 40
12
Figure 17. Example of Flat Jack
with Flashing
Figure 18. Example of 2½/12 Slant Jack
with Flashing
1.  Locate center of Roof Jack opening, measure 
13 1/2” from the rear wall of closet or alcove 
along the center line of furnace and fl oor 
opening. See Figure 19.
2.  Cut ceiling and roof holes as follows:
•  Ceiling = 8 3/4” (222 mm) diameter
•  Roof = 9 3/8” (238 mm) diameter
 IMPORTANT:
R e f e r   t o   t h e   i n s t a l l a t i o n 
i n s t r u c t i o n s   p r o v i d e d   w i t h 
o p t i o n a l   a i r   c o n d i t i o n i n g 
p a c k a g e s   w h e n   i n s t a l l i n g 
f u r n a c e s   w i t h   o p t i o n a l   c o o l i n g 
c o i l   c a b i n e t   o r   w i t h   o p t i o n a l 
C *   s e r i e s   i n d o o r   c o i l s .
Table 5. Slant Deck Flashings
Optional Deck Flashings for Flat and 2.5/12 Pitch Roof Jacks. 4/12 Pitch Roof Jacks not applicable.
ROOF JACK SERIES
IF ROOF PITCH IS:
SLANT DECK
FLASHING NUMBER
“X” FACTOR 
IS:
“F Series
2” in 12”
903893 (2.5/12)
2-1/8”
2-1/2” in 12”
903893 (2.5/12)
2-1/2”
3” in 12”
903894 (3/12)
2-7/8”
3-1/2” in 12”
903894 (3/12)
3-1/4”
4” in 12”
903895 (4/12)
3-5/8”
“S” Series (2.5 / 12 
Pitch only)
4-1/2” in 12”
903895 (2.5/12)
2-1/8”
5” in 12”
903895 (2.5/12)
2-1/2”
5-1/2” in 12”
903894 (3/12)
2-7/8”
6” in 12”
903894 (3/12)
3-1/4”
6-1/2” in 12”
903895 (4/12)
3-5/8”
CEILING
CUT-OUT FOR
FLUE AND 
ROOF JACK
C
L
C
L
24" 
20"
13 1/2" 
REAR WALL OF CLOSET OR ALCOVE
10"
FURNACE
OUTER
DOOR
FURNACE OUTLINE
Figure 19. Cut-Out Dimensions for 
Flue & Roof Jack
If the home is located in regions where snow 
accumulation exceeds 7” (HUD snowload zones) 
use an external roof jack extension (p/n 901937).
Extensions are optional accessories and may be 
purchased through your NORDYNE distributor.
Locating and Cutting Roof & Ceiling Openings
DO NOT ALLOW DEBRIS TO FALL INTO THE 
FURNACE. THIS COULD CAUSE UNSAFE 
OPERATION AND VOIDS THE FURNACE 
WARRANTY. Use the top cap that comes with 
the furnace packaging (or alternate protector) to 
prevent debris from falling into the furnace before 
the fi nal roof jack connection is made