Nordyne SERIES M1B Manuel D’Utilisation

Page de 40
24
Oil Gun Furnace with Honeywell R7184 / 
Beckett 7505 Control - M5S Models
1. When a call for heat is initiated, there is a 2 
to 6 second delay while the control performs 
a safe start check.
2. The ignition and motor are turned on and a 
fl ame should establish within a 15-second 
lockout time. NOTE: Burner will prepurge for 15 
seconds if equipped with Honeywell R7184B 
or Beckett 7505B Control.
3. If fl ame is not sensed within the 15-second 
lockout time, the control shuts down on safety 
lockout and must be manually reset by pushing 
the reset button on the control. If control locks 
over three times in a row, the control enters 
restricted lockout. To reset Honeywell R7184: 
Hold down the reset button for 45 seconds 
until the LED fl ashes once. Beckett 7505: Hold 
down reset button for 15 seconds until the red 
LED turns off and the yellow LED turns on.
 WARNING:
If furnace still doesn’t light, turn 
the furnace off as described above 
and call your technician. In the 
event of fl ashback or explosion, 
immediately shut off furnace and 
call your service technician.
4. After fl ame is established, the ignition remains 
on for 10 seconds to ensure fl ame stability. It 
then turns off.
5. The circulating air blower will energize after 
the temperature fan switch closes.
6. The furnace runs until the call for heat is 
satisfi ed.
7. The circulating air blower will de-energize when 
the temperature fan switch opens.
Gas Gun Models
1. On a call for heat, the furnace control begins 
an ignition sequence which lasts approximately 
45 seconds.
2. After this sequence, the control module tests 
to see if fl ame is sensed. If it has, the furnace 
continues to heat until the thermostat is 
satisfi ed.
3. If the burner has not lit, the ignition sequence 
is repeated a maximum of two more times. If 
fl ame is not sensed after three attempts, the 
control enters Lockout and no further attempts 
to light the burner will occur. If Lockout occurs, 
contact a qualifi ed service technician for 
assistance.
OPERATING SEQUENCE
Standing Pilot
1 On a call for heat, the thermostat contacts 
close, supplying 24 VAC to the gas valve.When 
energized, the valve steps open at a reduced 
fl ow and opens fully within 14 seconds.
2. When the call for heat is satisfied, the 
thermostat contacts open, shutting off gas fl ow.
Standing Pilot w/Induced Draft Blowers
1. On a call for heat, the thermostat contacts 
close, supplying 24 VAC to the relay.
2. The relay contacts close and the induced draft 
motor energizes.
3. When the inducer starts, the air pressure 
switch closes at -0.20 W.C. differential pressure 
and energizes the gas valve. The valve steps 
open at a reduced fl ow and opens fully after 
approximately 14 seconds.
4. When the call for heat is satisfied, the 
thermostat contacts open, the gas valve shuts 
off gas fl ow, and the induced draft blower stops.
M1M Models with Direct Ignition
1. On a call for heat, the thermostat contacts 
close, supplying 24 VAC between terminals 
C and W of the control module.
2. When the inducer starts, the air pressure switch 
closes at -0.20 W.C. differential pressure and 
energizes the gas valve.
3. After a 45 second purge, the ignitor is energized 
for a 30 second warm-up period. After warm 
up, the gas valve opens. NOTE: The time for 
ignition is approximately 6 seconds, after which 
the gas valve either remains open if fl ame is 
sensed, or closes if fl ame is not sensed.
5. If fl ame is not sensed, the sequence repeats 
four more times before a lockout occurs. To 
reset, wait 30 seconds and then interrupt the 
24 VAC power by turning the room thermostat 
below room temperature, then returning it to 
the original set point.
6. If fl ame does not establish on the 5th attempt 
(initial fi re + 4 re-tries), the control de-energizes 
the gas valve, the red LED fl ashes 4 times, 
and the furnace locks out heat operation for 
1 hour. See Table 9 (page 29).
7. If a fl ame is present, the control energizes the 
main blower on heat speed 30 seconds after 
the gas valve opens.
8. When call for heat is satisfi ed the thermostat 
contacts open, the gas valve shuts off gas fl ow 
and the combustion blower remains on for a 
30 second post-purge period.
9. The main blower is de-energized after a 120 
second blower off delay.