How to Shut Off Gas - Direct Ignition
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance 
before servicing unit.
3. Set the furnace On-Off Switch to OFF.
•  Honeywell (Figure 32): Turn gas control knob 
clockwise to OFF, Robertshaw (Figure 33): 
Push the gas control lever to OFF.
•  For oil, shut off all valves.
4. Replace the furnace door.
Operating Instructions for Oil Gun Furnaces
 
If your furnace model number begins with M5S*, 
the furnace is equipped with an ignition device 
which automatically lights the burner.
 
Do not try 
to light this furnace manually.
1. Open all valves in the oil line.
2. Verify the fi re door is closed.
3. Set the furnace On-Off switch to ON.
4. Set the thermostat to the desired setting.
NOTE: M5 oil gun furnaces may be converted to 
gas gun in the fi eld by using the proper conversion 
kit listed in the RPL.
Operating Instructions for Gas Gun Models
If your furnace model number begins with M1B, 
the furnace does not have a pilot. Ignition is 
accomplished by a silicon carbide hot surface 
ignitor. A control module takes care of all lighting 
and timing functions. There are no external 
relays or timing devices.
 
Do not try to light this 
furnace by hand. The control module is not 
fi eld serviceable.
1. Before operation, smell for gas all around the 
furnace, especially near the fl oor because 
some gases are heavier than air and will settle 
on the fl oor. If you detect gas, STOP and follow 
all the safety instructions.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Turn off the gas valve:
•  Honeywell: push in the gas control knob 
and turn clockwise to OFF (Figure 32).
•  Robertshaw: push the gas control lever to 
OFF (Figure 33).The lever cannot be placed 
in the off position unless it is pushed in 
slightly. DO NOT FORCE! 
5. Wait ten minutes to clear out any gas. If 
you smell gas, STOP! and follow the safety 
information. If gas is not detected, proceed to 
the next step.
6. Set  the  furnace On-Off switch to the ON 
position.
•  Honeywell: turn knob on gas control counter 
clockwise to ON.
•  Robertshaw: push the gas control lever to 
ON.
7. Turn electric power to the appliance ON.
8. Set the thermostat to HEAT and/or the desired 
temperature setting. The furnace should light 
in approximately 45 seconds. If the appliance 
will not operate, follow the instructions “How to 
Shut Off Gas - Direct Ignition Furnace” (page 
21) and call your service technician or gas 
supplier.
In the event of any fl ashback or explosion, 
immediately shut off the furnace and call your 
service technician.
How to Shut Off Gas - Oil & Gas Gun
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance at 
the breaker or fuse box.
3. Set the thermostat MODE switch to OFF.
4. Turn the gas valve OFF:
•  Honeywell: push in and turn the gas control 
knob clockwise to the OFF position (Figure 
32).
•  Robertshaw - push the gas control lever to 
the OFF position (Figure 33).
5. Replace the furnace door.
NOTE: M1B gas gun furnaces may be converted 
to oil gun in the fi eld by using the proper 
conversion kit listed in the RPL
Burner Adjustments
Burner settings are made at the factory. However, 
these settings may change during shipping, 
handling, and installation. The following items 
should be checked and readjusted if necessary.
Gas Pressure
The gas pressure can be checked with a 
manometer at the pressure tap located on the 
side of the gas valve. The gas valve pressure 
regulator can be adjusted by removing the 
regulator selector stack and turning the slotted 
insert located directly under the selector stack. 
The regulator selector stack must be secured 
in place before each pressure reading is taken. 
Natural gas manifold pressure should be 3.5” 
W.C. and L.P. gas manifold pressure should be 
10” W.C. Replace the gas pressure tap plug on 
the gas valve.
Pilot Flame (Standing Pilot Only)
The pilot fl ame can be adjusted by turning the 
pilot adjustment screw, located on top of the 
gas valve (See Figure 30, page 20). The pilot 
fl ame height should be between 3/4” and 1.” The 
fl ame tip should be visible just above the pilot 
bracket when viewed through the observation 
door. The same pilot orifi ce is used with both 
natural and LP gas.