Sterling SDA 150-380 Manuel D’Utilisation

Page de 52
 
 
Cabinet Series Dehumidifying Dryer 
 
16 
Indicator 
Name 
Description 
compressed air, the pressure switch opens and sends 
a signal to the PLC controller to shut down dryer 
operation.  Dryer operation automatically resumes 
when 80 psi (551 kPa/ 5.51 bars) air is restored. 
R
 
High Temp 
Process Air Light 
The High Temp Process Air alarm indicator lights 
when the temperature at the process air 
thermocouple is above the high alarm set value. 
Upon high temperature alarm condition the process 
heaters turn off, the process blower remain on. 
The alarm mode and value are factory-set to track 
25º above the process set point. The alarm value is 
an upper-limit deviation above the process set point. 
When the temperature at the process thermocouple 
returns to within the acceptable range, the alarm 
output de-energizes and all heaters turn on again 
automatically. 
R
 
High Temp 
Regen Air Light 
The High Temperature Regen Air alarm indicator 
lights when the thermostat above the regeneration 
heater assembly senses an abnormally high 
temperature. 
The regeneration heaters shut down until the 
temperature falls below the alarm point. The 
regeneration blower continues to run for cooling the 
heaters and desiccant bed. The alarm condition 
clears when the temperature drops below the 
thermostat setpoint. The heaters re-energize 
automatically. 
A
 
High Dew Point 
Light 
The High Dew Point alarm indicator lights when the 
process air delivery dew point exceeds a dew point 
of -10
°F (-23°C). 
G
 
Material Loading 
Light 
The Material Loading indicator lights when material 
is being conveyed. 
A
 
Optional Dirty 
Filter Light 
If installed, the Dirty Filter alarm indicator lights 
when the pressure differential across the process, 
regeneration and conveying air return filter exceeds 
the pressure switch setting. Service the filter when 
this indicator lights. The indicator and the alarm 
condition clears after you service and reinstall the 
filter.