3
2.2 Wiring
 WARNING!
 
DO NOT ALLOW THE YELLOW 
WIRE FROM THE ULTRA-AIRE DEHUMIDIFIER TO CONTACT 
THE RED OR WHITE WIRES FROM THE ULTRA-AIRE 
DEHUMIDIFIER, DAMAGE TO THE 24-VOLT TRANSFORMER 
WILL RESULT.
 WARNING!
 
THE REMOTE CONTROL OF THE 
ULTRA-AIRE DEHUMIDIFIER OPERATES ON A LOW VOLTAGE 
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE 
CONNECTED TO A HIGH VOLTAGE CIRCUIT.
 WARNING!
 
UNPLUG THE ULTRA-AIRE 
DEHUMIDIFIER BEFORE WIRING THE DEH 3000R.
The installer must supply all field wiring, including the 
wiring between the Ultra-Aire dehumidifier and the DEH 
3000R. Some of the control wires leaving the Ultra-Aire may 
not be used in some control situations and should be left 
disconnected with wire nuts taped onto the stripped ends.
Be sure to consult the electrical schematic in this manual or 
the internal electrical box of the Ultra-Aire dehumidifier before 
making any control connections.
 WARNING!
 
ONLY CONNECT THE WHITE WIRE 
TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH 
AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER 
DAMAGE MAY RESULT.
The White wire controls the optional motorized damper 
that can be installed into a fresh air duct. This damper 
provides the ability to control fresh air ventilation using 
the ventilation timer function of the DEH 3000R and 
the terminal labeled 
“DMP” on the DEH 3000R (See 
Section 3.8). Leave the 
“DMP” terminal unused if a 
motorized damper is not used, and cap off the White 
wire from the Ultra-Aire dehumidifier.
Standard wire colors for thermostats are as follows:
Description 
Color 
Terminal code
24VAC 
Red 
R
Call for Heat 
White 
W or W1
Force Fan On 
Green 
G
Compressor 
Call for Cooling 
Yellow 
Y or Y1
2.3 Auxiliary relay operation
It may be desirable to coordinate fan operation of the central 
heating/cooling system with dehumidifier operation. The DEH 
3000R contains a relay that provides this ability. 
The relay terminals labeled NC, COM and NO operate according 
to the following chart:
DEHUMIDIFIER 
COM to NO 
 COM to NC
ON 
CONNECTED 
 OPEN
OFF  
OPEN 
CONNECTED
Common uses (assuming standard thermostat wiring colors as 
noted):
Lock-out the A/C during dehumidification
This will turn off the A/C whenever the dehumidifier runs.
1.  Wire the Yellow thermostat terminal to the NC terminal on 
the DEH 3000R.
DEH 3000R Dehumidifier & Ventilation System Controller
 Installation, Operation & Service Manual