2.5 Testing
Verify the wiring connections.
 WARNING!
 
ONLY CONNECT THE WHITE WIRE 
TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN 
ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE 
MAY RESULT.
After checking the wiring, this short test will confirm proper 
hook-up.
1.    Install front cover of the DEH 3000R; connect the top first, 
then the bottom.
2.    Plug in the Ultra-Aire dehumidifier. The DEH 3000R should 
power up.
3.    Turn the DEH 3000R ON by pressing the 
“ON/OFF” button.
4.    Verify dehumidification operation by adjusting the RH 
“SETPOINT” to below the “%RH” reading on the display. 
Use the down 
“RH” button. Confirm Ultra-Aire fan and 
compressor operation. Both should be ON now.
Increase the RH 
“SETPOINT” on the display to well above the 
“%RH” reading on the display. Press the “RH” up arrow to 
increase the RH 
“SETPOINT”.
After running the dehumidifier compressor the DEH 3000R 
applies a 10 minute restart lockout on all functions. You will 
have to wait for the restart lockout to expire.
5. Verify FAN-only operation:
a.  Check the 
“VENT” mode on the display, it will either 
be 
“CLOSED” or “OPEN”. If it is “CLOSED” go to the 
next step. If it is 
“OPEN”, press and hold the “VENT” 
key until “
OPEN” flashes on the display, release the key 
and then press it one more time. 
“OPEN” will change to 
“CLOSED”. Don’t touch the keys for several seconds until 
it stops flashing.
b.  Press and hold the 
“FAN” button until “AUTO” begins 
flashing on the display, release it, and then press it again 
to switch the fan to the 
“ON” setting.
c.  Confirm that the Ultra-Aire fan is ON. Ultra-Aire 
compressor must be OFF. Ventilation damper (if used) 
should be CLOSED.
6. Verify optional VENT operation (if electric damper is installed):
a.  Press and hold the 
“FAN” button until “ON” flashes on 
the display.
b.  Release the 
“FAN” button, then press it again to switch 
fan operation to 
“AUTO”.
c.  Press and hold the 
“VENT” button until “CLOSED” 
flashes on the display.
d.  Release the 
“VENT” button, then press it again to switch 
vent mode to 
“OPEN”.
e.  Confirm that the Ultra-Aire fan is ON. Ventilation damper is 
OPEN. Ultra-Aire compressor must be OFF.
f.  Press and hold the 
“VENT” button until the “OPEN” 
flashes on the display.
g.  Release the 
“VENT” button, then press it again to switch 
vent mode to 
“CLOSED”.
 WARNING!
 
DO NOT MAKE ANY OTHER 
CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.
7.  Verify any additional optional control operations such as fan 
interlock or A/C lockout.
8. Proceed to the Operation section.
2.6 Troubleshooting
FOR THE HVAC PROFESSIONAL:
n
 
No display on initial start up.
Note: This is often the result of a drained capacitor. The 
capacitor will recharge once power is applied or re-applied to 
the unit.
– Verify unit has power.
– Turn unit off then on.
–  Disconnect the unit from power source then re-apply 
power to the unit. Display should now operate.
Function not working properly.
–  Verify wiring.
–  Verify voltage with voltmeter.
Dehumidifier not working properly.
–  See chart below:
Wire connections  
Operation
Yellow & Blue  
Fan & Compressor
Yellow & Green 
Fan Only
5
DEH 3000R Dehumidifier & Ventilation System Controller
 Installation, Operation & Service Manual