Emerson M22 Manuel D’Utilisation

Page de 47
 
36 
MAN-0076 Rev 05 Millennium II 
December 07, 2012 
Net Safety Monitoring Inc 
Sensor Status Registers, Transmitter Status LED, Current output and Meaning 
Table 6 below, shows the sensor status registers, and the transmitter’s current output, along with corresponding status 
LED and meaning. 
Note: To differentiate between conditions resulting in 2.5 mA, view the Event Log. See Event Log menu option. 
 
    
Table 6: Current output and meaning 
   
Reg. 
Value 
Current Output 
(mA) 
Status LED 
Meaning 
Red 
Green 
4 – 20 
Slow Flash           
(Gas found) 
Flash                      
(No Gas) 
Normal Sensor operation – regularly calculates 
gas concentration. 
3.0 
 
Solid 
Sensor is zeroing itself ( Cal Mode) 
3.3 
Very Fast 
Flash 
 
Sensor is waiting until it detects application of 
cal gas. 
3.3 
Very Fast 
Flash 
 
Sensor waits until gas level stabilizes, then 
begins spanning. 
3.6 
 
Solid 
Spanning is complete, user asked to remove gas. 
3.6 
 
Solid 
Displayed for 4 seconds once gas decreases to 
3% FS after user asked to remove cal gas. 
2.5 
Very Fast 
Flash 
 
Sensor is not calibrated, requires user to 
calibrate. 
3.0 
Slow Flash 
 
Sensor is waiting for 90 seconds to allow the 
signal to stabilize ( Start Delay) 
3.0/3.3 
Solid 
Solid 
Signal was too unstable to acquire accurate zero 
after 90 seconds  
10 
3.0/3.3 
Solid 
Solid 
Displayed for 4 seconds is the cal gas was 
removed prematurely OR is a 90 second time 
limit has elapsed and the signal was too 
unstable to acquire accurate data  
11 
4 – 20 
Fast Flash 
 
See Event Log in transmitter main menu. 
12 
4 – 20 
Fast Flash 
 
See Event Log in transmitter main menu.  
13 
2.5 
Fast Flash 
 
FAULT DETECTED: Input voltage <8V. 
14 
2.5 
Fast Flash 
 
FAULT DETECTED: Input voltage >33V.