Emerson M22 Manuel D’Utilisation

Page de 47
 
38 
MAN-0076 Rev 05 Millennium II 
December 07, 2012 
Net Safety Monitoring Inc 
Table 7: Modbus Registers 
Reg# 
Meaning 
Readable 
Writeable 
40001 
Concentration value as calculated by sensor 
(RTUsensor_out), Channel 1 
 
40002 
Sensor status (RTUsensor_stat), Channel 1 
 
40003 
Temperature of sensor element housing in Kelvin 
(RTU temperature), Channel 1 
 
40004 
RFU, Channel 1, always read as 0x0000 
 
40005 
RFU, Channel 1, always read as 0x0000 
 
40006 
Concentration value as calculated by sensor 
(RTUsensor_out), Channel 2 
 
40007 
Sensor status (RTUsensor_stat), Channel 2 
 
40008 
Temperature of sensor element housing in Kelvin 
(RTU temperature), Channel 2 
 
40009 
RFU, Channel 2, always read as 0x0000 
 
40010 
RFU, Channel 2, always read as 0x0000 
 
40011 
Concentration value as calculated by sensor 
(RTUsensor_out), Channel 3 
 
40012 
Sensor status (RTUsensor_stat), Channel 3 
 
40013 
Temperature of sensor element housing in Kelvin 
(RTU temperature), Channel 3 
 
40014 
RFU, Channel 3, always read as 0x0000 
 
 
40015 
RFU, Channel 3, always read as 0x0000 
 
 
40016 
Concentration value as calculated by sensor 
(RTUsensor_out), Channel 4 
 
40017 
Sensor status (RTUsensor_stat), Channel 4 
 
40018 
Temperature of sensor element housing in Kelvin 
(RTU temperature), Channel 4 
 
40019 
RFU, Channel 4, always read as 0x0000 
 
40020 
RFU, Channel 4, always read as 0x0000 
 
**40021 
Transmitter Status  
 
40022 To 40090 
RFU 
 
 
40091 
Initialize Quick calibration, channel 1 to 4 
40092 
Initialize Normal Calibration, channel 1 to 4 
NOTE: Alarm points can be set up through MPDBUS registers 40093 to 40096 
40093 
Channel 1 high alarm limit 
40094 
Channel 1 low alarm limit 
40095 
Channel 2 high alarm limit 
40096 
Channel 2 low alarm limit 
40097 
RFU, Channel 3 high alarm limit 
40098 
RFU, Channel 3 low alarm limit 
40099 
RFU, Channel 4 high alarm limit 
40100 
RFU, Channel 4 low alarm limit 
40101 
Reset latch relays 
 
*RFU – Reserved for future use 
** The transmitter Status register (Register 40021) is a bit flag register.  Table 8 
on next page, shows the detailed meaning of 
each bit in the register.