Net Safety Monitoring Inc 
   Table 8: Transmitter Status Register value and meaning 
Bit 
Meaning 
0x0000 
Normal Sensor operation – no fault or alarm has happened 
0x0001 
Channel 1 sensor fault status tripped.  Communication Fault, Calibration Fault, etc 
0x0002 
Channel 1 Low Alarm tripped 
0x0004 
Channel 1 High Alarm tripped 
0x0008 
Channel 2 sensor fault status tripped.  Communication Fault, Calibration Fault, etc 
0x0010 
Channel 2 Low Alarm tripped 
0x0020 
Channel 2 High Alarm tripped 
0x0040 
Channel 1 needs Calibration 
0x0080 
Channel 2 needs Calibration 
5.5 HART Communication  
The  HART  protocol  is  a  powerful  communication  technology  enabling  users  to  exploit  the  full  functionality  of  the 
Millennium II Transmitter. The HART communication option is only available with the single channel version of 
the Millennium II Transmitter. The Millennium II Transmitter is a generic device that will work with other universal 
communication devices.  
The HART Communicator may be connected to the single channel Analog/HART model Millennium II Transmitter 
via the HART Port connector (HPT-001) which provides the necessary interface for communication. The HART Port 
connector is fitted to one of the ¾” NPT conduit entries and its communication wires fitted to the HART Pins located 
at J5 near the ribbon cable on the underside of the display/CPU assembly. The HART Communicator probe wires 
(leads) are then connected to HART Port connector contact points. HART Communication may also be done remotely 
using a designated Net Safety Multipurpose Junction box (JB-MPH-A/S). See the HART Port connector manual 
(MAN-0083) for more details. When remote HART Communication is being done, ensure the HART jumper is 
connected across pins at J5 near ribbon cable on display/CPU assembly. By default the jumper is connected across 
pins. The HART Communicator can be connected directly in the 4-20mA signal wiring across a 250 - 600 Ohm 
resistor. Do not install resistor within transmitter. See Figure 20. 
 
Figure 20: Analog/HART wiring