VENTING AND INSTALLATION
Vent System Approvals
Figure 8 shows the vent termination caps and systems approved 
for  use  with  these  models. Approved  vent  system  terminations 
are  labeled  for  identification.  3-inch  diameter  listed  flexible 
aluminum or stainless steel gas vent is used for both the incoming 
combustion air and exhaust vent pipes. NO OTHER VENTING 
SYSTEMS  OR  COMPONENTS  MAY  BE  USED.  Detailed 
installation instructions are included with each vent termination 
kit and should be used in conjunction with this manual.
Horizontal Venting
The  vent  system  on  this  model  CANNOT  be  terminated 
horizontally.
Vertical Venting
The  inlet  and  exhaust  vent  pipes  MUST  be  connected  to  the 
proper collars on the unit 
AND to the termination cap or the unit 
will not operate. The intake vent collar is identified by a stamped 
“I” on the top collar sliding vent plate assembly.
WARNING: MAJOR U.S. BUILDING CODES SPECIFY 
MINIMUM  CHIMNEY  AND/OR  VENT  HEIGHT 
ABOVE THE ROOF TOP. THESE MINIMUM HEIGHTS 
ARE  NECESSARY  IN  THE  INTEREST  OF  SAFETY. 
SEE  FIGURES  8  THROUGH  10  FOR  MINIMUM 
HEIGHTS, PROVIDED THE TERMINATION CAP IS 
AT LEAST 2-FEET FROM A VERTICAL WALL AND 
2-FEET BELOW A HORIZONTAL OVERHANG.
Note: This also pertains to vertical vent systems installed on the 
outside of the building.
WARNING:  THE  EXHAUST  PIPE  MUST  ONLY 
BE  CONNECTED  TO  THE  EXHAUST  STARTING 
COLLAR  OF  THE  UNIT  AND  TO  THE  EXHAUST 
COLLAR OF THE TERMINATION CAP.
THE INLET AIR PIPE MUST ONLY BE CONNECTED 
TO  THE  INLET AIR  STARTING  COLLAR  OF  THE 
UNIT  AND  TO  THE  INLET  AIR  COLLAR  OF  THE 
TERMINATION CAP. BOTH THE INLET VENT AND 
THE  FLUE  VENT  MUST  BE  CONNECTED  FROM 
THE INSERT TO THE VENT TERMINATION CAP.
NOTE:  The  minimum  vertical  vent  rise  is  12  feet  and  the 
maximum  vertical  vent  rise  is  35  feet.  These  dimensions  are 
measured from the starting collars of the unit to the end of the last 
section of vent pipe. See Figure 8.
NOTE:  
The  damper  of  the  masonry  chimney  may  need  to  be 
removed to allow installation of the flexible-vent pipe.
When installing into a zero clearance, factory built wood-burning 
fireplaces, the use of the DVKI Round Vertical Termination Kit 
should allow you to mount the vent adaptor and cap to the exposed  
round chimney pipe easily.
Connecting the Vent Pipe
Caution: Sharp edges. Always use gloves when installing.
Install the 3-inch flexible vent pipes down through the chimney.
Attach  the  pipe-to-cap  adaptor  to  the  termination  cap  and  the 
top of the flexible vent pipe, then install the cap to the top of the 
chimney. 
Remove the vent slide plate assembly from the top of the insert. 
See  Figure  7.  Trim  off  excess  venting  then  attach  and  secure 
the bottom ends of the flex pipes to the starting collars with the 
adjustable band clamps provided. Slide the gas insert into place, 
and position any excess flex vent pipe back up into the chimney. 
Begin installation of the insert into the fireplace opening. Align 
the vent slide plate assembly with the guides located on top of 
the insert. Work the insert inch by inch into the fireplace cavity 
as you pull forward on the vent slide plate assembly. Do not use 
excessive force on the vent slide plate. Once the vent slide plate 
is close to seating, install the vent bolt through the center hole 
of the insert top flange, and into the vent slide plate nut. Using 
a wrench or socket, tighten the bolt until the vent slide plate is 
seated forward completely. 
Positioning, Leveling, and Securing Insert
1.  Place the insert into position.
Note: The front flanges of the insert (without surround panels) 
should be set at approximately 1”(inch) in front of the face of the 
fireplace.
2.  Level the insert from side to side and front to back.
3.  If necessary, use the leveling bolts included in the instruction 
pack. Screw the legs into the nuts installed in the bottom of 
the insert. Turn legs in until insert is level.
CAUTION: TO AVOID DOWNDRAFTS AND/OR COLD AIR 
PROBLEMS, IT IS RECOMMENDED TO SEAL OFF THE 
AREA BETWEEN THE TERMINATION CAP AND THE TOP 
OF THE SOLID-FUEL CHIMNEY OPENING INTO WHICH 
THE VENT CAP HAS BEEN INSTALLED.
Figure 7