Vertical Through the Roof Applications
The Gas Fireplace Insert has been approved for:
a)  Vertical installations up to 35 feet in height (top of insert to 
cap).
b)  Two sets of 45 degree elbow offsets (bends in flexvent) within 
the vertical installation. From 0 to a maximum of 8 ft. of vent 
pipe can be used between elbows.
c)  Wall straps must be used to support offset pipe every 4'. 
This application will require that you first determine the roof pitch 
and use the appropriate venting components.
General Maintenance
Conduct  an  inspection  of  the  venting  system  semi-annually. 
Recommended areas to inspect are as follows:
1.  Check areas of the venting system which are exposed to the 
elements  for  corrosion.  These  will  appear  as  rust  spots  or 
streaks and, in extreme cases, holes. These components should 
immediately be replaced.
2.  Remove the cap and shine a flashlight down the vent. Remove 
any bird nests or other foreign material.
3.  Check  for  evidence  of  excessive  condensate,  such  as  water 
droplets forming in the flex venting and subsequently dripping 
out at joints or seams. Condensate can cause corrosion of caps, 
pipe and fittings. It may be caused by having excessive lateral 
runs, or having exterior portions of the system exposed to cold 
weather.
4.  Inspect joints to verify that no pipe sections or fittings have been 
disturbed and, consequently, loosened. Also, check mechanical 
supports, such as wall straps or plumbers’ tape for rigidity. 
Determining Minimum Vent Height Above the Roof.
WARNING:  Major  U.S.  building  codes  specify  minimum 
chimney and/or vent height above the roof top. These minimum 
heights are necessary in the interest of safety. These specifica-
tions are summarized in Figure 9.
Figure 9
Note that for steep roof pitches, the vent height must be increased. 
In high wind conditions, nearby trees, adjoining roof lines, steep 
pitched roofs, and other similar factors can result in poor draft, 
or down-drafting. In these cases, increasing the vent height may 
solve this problem.
When terminating the vent cap near an exterior wall or overhang, 
maintain minimum clearances as shown in Figure 10.
ROOF PITCH
H (Min.)
Flat to 6/12
12" (305 mm)
6/12 to 7/12
15" (381 mm)
Over 7/12 to 8/12
18" (457 mm)
Over 8/12 to 16/12
24" (610 mm)
Over 16/12 to 21/12
36" (914 mm)
VERTICAL TERMINATION
Figure 10
MIN.
12" MIN.
24"
24"
MIN.
CL