www.enviromaster.com
5
multi-zone Heat Pump Condensing units
S2HB ElEctrIcAl WIrIng InStAllAtIon SEctIon
3. Use only HACR type breakers or time 
delay fuses. Select the wire size accord-
ing to the ampacity rating. 
4.  To  access  electrical  connections  and 
wiring diagram:
a) Remove the screws on the side panel 
adjacent to the back panel.
b)  The  screws  adjacent  to  the  front 
panel should already be loose (don't 
remove them).
1. All electrical wiring must be run according 
to NEC and local codes. 
2. Refer to the unit rating plate for voltage, 
minimum circuit ampacity and over cur-
rent protection requirements. 
c. Slide the side panel out to access the 
high/low  electrical  connections  and 
wire diagram.
Note: Remove the plastic edge guards 
from the holes and replace with a water-
tight 
strain relief fitting
 (High V) and a 
split grommet fitting (low V)
5. Power should be run to a weather proof 
disconnect box usually within 3 feet of 
the unit.
6. From the disconnect box, run the power 
through the 7/8" hole on the side of the 
unit and into the electrical box and an-
chor with the strain relief fitting. 
7. Run wires to the high Volt pigtail in the con-
trol box and attach L1 and L2 connections. 
Also run green wire to ground wire.
The  EMI   America  Series  condensing 
unit must:
• Be connected to a properly grounded 
electrical supply with the proper voltage 
as stated on the rating plate.
• Have proper over current protection (i.e. 
time- delay fuse/HACR-Breaker) as listed 
on the Rating Plate.
Failure to follow these instructions can re-
sult in a fire, explosion, or electrical shock 
causing property damage, personal injury, 
or death.
 dAngEr
!  
 
Do  not  use  the    EMI   America  Series 
condensing unit with any electrical supply 
voltage other than the one listed on the 
rating plate.
Check the rating plate on the unit for the 
correct voltage rating.  Failure to use the 
correct voltage may result in death, serious 
bodily injury or property damage.  If you have 
any questions or doubts, consult the factory 
before installing this unit.
 dAngEr
!  
 
Rating 