Emerson 3000/ITR Manuel D’Utilisation

Page de 72
Component Operation and Maintenance
47
7.4.11 Compressor Oil
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system 
damage.
Failure to use oil types, viscosities and quantities recommended by the compressor 
manufacturer may reduce compressor life and void the compressor warranty. See oil types 
specified in Table 10
• Do NOT mix polyol ester (POE) and mineral-based oils.
• Do NOT mix oils of different viscosities.
Consult Emerson or the compressor manufacturer if you have questions.
1. Use Copeland POE Oil ULTRA 22CC, Mobil EAL Arctic 22CC or other Copeland-approved oils.
7.5
Compressor Replacement
Replacement compressors are available through your local Emerson office. Compressors are shipped 
in reusable packaging. If unit is under warranty, complete and include Liebert Service Credit Appli-
cation (LSCA) with the compressor that is being returned. The original compressor should be 
returned in the same packaging.
Before Replacing or Returning a Compressor
Be certain that the compressor is actually defective. At a minimum, recheck a compressor returned 
from the field in the shop or depot for Hipot, winding resistance and ability to start before returning 
it. More than one-third of compressors returned for warranty analysis are determined to have nothing 
wrong. They were misdiagnosed in the field as being defective. Replacing working compressors unnec-
essarily costs everyone.
7.5.1 Compressor Functional Check
The following diagnostic procedure should be used to evaluate whether the compressor is working 
properly.
1. Proper voltage to the unit should be verified.
2. The normal checks of motor winding continuity and short to ground should be made to determine 
if the inherent overload motor protector has opened or if an internal motor short or ground fault 
has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to 
allow it to reset.
3. Proper indoor and outdoor blower/fan operation should be verified. Condenser glycol flow should 
be verified.
4. With service gauges connected to suction and discharge pressure fittings, turn On the compressor. 
If suction pressure falls below normal levels, either the system charge is low on or there is a flow 
blockage in the system.
5. If suction pressure does not drop and discharge pressure does not rise to normal levels, reverse 
any two of the compressor power leads and reapply power to make sure compressor was not wired 
to run in reverse direction. If pressures still do not move to normal values, system is properly 
charged and solenoid valves function, the compressor is faulty. Reconnect the compressor leads as 
originally configured and use normal diagnostic procedures to check operation of the reversing 
valve.
6. To test if the compressor is pumping properly, the compressor current draw must be compared to 
published compressor performance curves using the operating pressures and voltage of the 
system. If the measured average current deviates more than ±15% from published values, a faulty 
compressor may be indicated. A current imbalance exceeding 15% of the average on the three 
phases should be investigated further.
Table 10
Compressor oil types
Compressor Type
R-407c
Copeland Scroll
and Digital Scroll
POE Oil - ISO 22 
Viscosity