Component Operation and Maintenance
51
Changing Humidifier Lamps
1. Open disconnect switch.
2. Open front panel.
3. Remove screws securing line voltage compartment cover, then remove the cover.
4. In line voltage compartment, disconnect one end of the purple jumpers, then locate the burned out 
bulb with a continuity meter.
5. Remove humidifier pan. Refer to Removing the Pan on page 50.
6. Remove lamp brackets (2) under lamps.
Figure 26 Infrared humidifier lamps
7. Loosen two screws securing bulb wires to junction block.
8. Pull bulb straight down.
9. Replace bulb. Wrap wires once loosely around bulb. This will support the bulb and also allow for 
thermal expansion. Make sure lamp wires are secure in the junction block.
NOTICE
Risk of oily deposits. Can shorten component life.
Do not touch the quartz lamps with your bare hands. Oily deposits such as fingerprints will 
severely shorten bulb life. Use clean cotton gloves at all times.
10. Reverse Steps 1 through 6 to reassemble.
Autoflush Infrared Humidifier Cleaning System
NOTICE
Risk of improper water pressure. Can cause improper component operation.
To operate properly, the Autoflush Humidifier requires a water source that can deliver at 
least 1 gpm (0.063 l/s) with a minimum pressure of 20 psig (138 kPa).
The autoflush system will periodically flush the humidifier pan with water to prevent the buildup of 
water minerals due to saturation. Because water conditions vary, the amount of water flushing 
through the system may be programmed to match local needs.
Water amounts between 110% and 500% of the amount needed for humidification may be selected. 
Operation of the flushing system is then automatic and no further adjustments need to be made.
Autoflush Operation
The operation of the autoflush is divided into four steps, beginning with a call for humidification.
1. If the humidifier has not been activated for over 30 hours, the autoflush will flow water into the 
pan for about 30 seconds. This will provide a minimum amount of water in the pan and prevent 
heat damage to the humidifier pan. Humidifier lamps are Off.
2. If the humidifier has been activated within the last 30 hours, Step 1 is bypassed. The autoflush 
will flow water into the pan for about 4 minutes. The humidifier lamps are On and the humidifier 
is operational during this period. When the pan is filled (the fill cycle has timed out), the water 
make-up valve is closed.
3. The water make-up valve remains Off and the humidifier lamps are On for a maximum of 
9-1/2 minutes.
4. After the 9-1/2 minute delay, the autoflush adds water to the pan to replenish the water used in 
humidification and flush the pan of mineral solids. This amount of water is adjustable from 110% 
to 500% in increments of 10%. At the end of this cycle, the make-up valve is closed. Steps 3 an4 
repeat as long as humidification is required.
Humidifier Lamps