Emerson 3000/ITR Manuel D’Utilisation

Page de 72
Component Operation and Maintenance
52
Autoflush Controls
Use the LCD display, menu, and keys on the front control panel to program the autoflush controls.
7.7.2 Steam Generating Humidifier
Steam generating humidifiers are designed to operate in voltage ranges from 200 to 575 volts and 
generate 11 pounds (5 kg) of steam per hour. These humidifiers operate efficiently over a wide range 
of water quality conditions and automatically adjust to changes in the conductivity of water. The 
humidifiers drain and refill to maintain an amperage setpoint and alert the operator when the 
humidifier canister needs to be replaced. The humidifier is in the lower section of upflow units; it is in 
the middle section of downflow units.
Figure 27 Steam generating humidifier