Troubleshooting
60
Table 18
Steam generating humidifier troubleshooting
Symptom
Possible Cause
Check or Remedy
False canister full indication
Foaming
Check drain valve to ensure that it drains freely. Check and 
replace if defective.
Check water supply. If commercially softened, reconnect to 
raw water supply. If connected to hot water reconnect to 
cold water.
Main 24 VAC fuse or circuit 
breaker trips
Shorts or loose connections
Check the wiring connections of the 24 VAC circuit.
Faulty circuit board
Replace the circuit board.
Main fuses blow 
approximately 15 seconds 
after unit is activated
Faulty solenoid
Check for magnetic field at coil.
Conductivity too high
Check amp draw of humidifier on startup. If it exceeds rated 
amps, increase setting of the % pot on the circuit board
Main fuses blow when 
drain valve is activated.
Mineral deposits obstruct 
drain valve
Check drain valve for obstructions and clean if necessary.
Faulty solenoid
Check for magnetic field at coil.
Faulty circuit board
Replace circuit board.
Unit On, humidifier will not 
operate
Humidifier not receiving power
Verify that RUN/DRAIN switch is in the RUN position.
Check fuses or CBs and replace or reset if necessary.
Make sure molex connector is securely plugged into circuit 
board and that no wires are loose.
Contactor pulled in, but no 
water enters canister
No water available to unit
Check external shutoff valves.
Clogged fill line strainer
Clean or replace fill line strainer.
Wiring breaks or loose 
connections
Check for faulty wiring and loose connections.
Faulty circuit board
Replace circuit board.
Water enters canister, but 
canister full circuit activates 
at a low water level
Foaming
Check drain valve and water supply.
Canister interface connections 
incorrect
Check connection on component plate in humidifier cabinet. 
Terminal #1 on the square block interface device must be 
connected to L2 of the power terminal block. L2 must also 
be connected to the electrode closest to the steam outlet 
port.
Verify that the red wire from Terminal #2 on the interface 
connects to the red top terminal on the canister. This is the 
one farthest from the steam outlet port and is the high water 
sensor probe.
Full isolation has broken down
Remove red canister full wire from canister. If normal 
operation resumes, canister must be replaced. Remove the 
wire from Terminal #3 on the interface. If normal operation 
resumes, canister full interface must be replaced.
Drain assembly not operating 
freely
Check and replace coil or valve if necessary.
Faulty circuit board
Replace circuit board
Canister fills but overflows
Canister full circuit does not 
activate
Check wiring of canister full interface. Replace circuit board.