Emerson 3000/ITR Manuel D’Utilisation

Page de 72
Troubleshooting
61
Excessive arcing in the 
canister
Drain valve clogged or 
defective
Verify that drain valve operates freely when activated. Clean 
valve and replace coil or valve if defective. Flush canister 
several times and replace if arcing persists.
Improper water supply
If water is commercially softened, reconnect humidifier to 
raw water supply, drain canister, and restart If connected to 
hot supply, reconnect to cold water.
Insufficient drain rate
Increase drain rate by adjusting % pot on circuit board 
above the preset 70% to roughly 80%.
Excessive iron content in 
water
Analyze iron content of water. If it exceeds 0.1 mg./l, install 
a filter to remove iron from water supply.
On cold startup, canister 
fills, high water alarm 
activates and humidifier 
fails to reach full amperage
Conductivity of water too low
Drain canister and add one Alka-Seltzer tablet to canister. 
Refill. Turn the % pot to roughly 60%. Restart humidifier. If 
amperage rises rapidly, it may be necessary to dilute the 
water to prevent blown fuses. If it rises too slowly, add 
another Alka-Seltzer tablet.
On cold startup, canister 
fills, high water alarm 
activates and humidifier 
fails to reach full amperage
Fill solenoid not closing tightly
If humidifier returns to canister full condition, verity that the 
fill solenoid closes tightly.
Table 19
Reheat troubleshooting
Symptom
Possible Cause
Check or Remedy
Reheat will not operate; 
contactor not pulling in
Control not calling for heat
Check monitor status.
Reheat safety stat open
Jumper between terminals P34-1 and P34-2. If reheat operates, 
safety is open. Remove jumper. Replace safety.
Reheat not operating; 
contactor pulling in
Heater burned out
Turn Off power and check heater continuity with Ohm meter.
NOTE:
Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections 
are necessary to ensure proper cleanliness of the reheating element. Should inspection reveal 
corrosion particles on the reheating element or adjoining surfaces (including ducts and 
plenums), appropriate cleaning should be performed. Periodic reheating element replacement 
may be required to meet specific application requirements.
Table 18
Steam generating humidifier troubleshooting (continued)
Symptom
Possible Cause
Check or Remedy