Friedrich RC/RH 10 Manuel D’Utilisation

Page de 26
10
www.retroaire.com
The Right Fit For Comfort
Hydronic Only: Remove the 2-position connector as-
sembly from kit bag supplied with unit (this will have 2 
yellow wires attached). Connect this 2-position connec-
tor to the 2-position connection located on the bottom 
of the control box panel. 
To Connect Aquastat: 
A. Remove the black jumper wire located on the 
bottom panel of the control box (this is also ter-
minated with a 2-position connector).
B. Cut the jumper wire in the middle and splice the 
aquastat to the jumper. 
C. Place the connecter back into  original location. 
Refer to wire diagram on the unit for details.
8. Connect line cord. 
9. See Final Inspection and Startup on page 20.
6. 1” x 1” Open cell foam strips  are provided to prevent 
outside air from entering around the chassis to the room 
from the sides and top of the cabinet. Install between 
wall sleeve and cooling chassis. It is imperative to have 
a solid air seal between wall sleeve and chassis. Failure 
to do so will result in air leakage from outdoor to indoor 
causing system problems i.e. coils freezing, short cy-
cling, and constant running of unit. If installer is in need 
of more foam than supplied in kit, consult factory.
RC/RH 20 PERFORMANCE DATA*
Unit 
Size
Cooling 
Btuh
EERs Heat Pump 
Btuh
COP
Fresh Air 
CFM
9
9,500
10
8500
2.8
40/35
12
11,900
10
11400
2.9
40/35
15
14,700
9.2
13800
2.8
40/35
18
16,900
9.1
N/A
N/A
40/35
RC/RH20 Hydronic Heat *
Performance 104-101 (Single Row Coil)
GPM
EWT (°F)
Capacities Btuh
P.D.
3.0
180°F Hi
16,400
4.4
180°F Lo
15,400
4.4
140°F Hi
10,300
4.6
140°F Lo
9,700
4.6
RC/RH20 INSTALLATION INSTRUCTIONS
 
(Continued)
*Refer to the charts on page 23 for electrical and optional electric heat specifi cations.
7. Once confi dent that all seals are the correct size and in 
the proper location and the correct baffl es are attached 
to  the  condenser  coil  in  the  proper  orientation,  slide 
unit into fi nal position and tighten any tie down bolts or 
screws as necessary.
Figure D4
Front View
Cooling Chassis
Wall Sleeve
1�x1� Foam Tape